Installing A Remote Keyswitch; Figure 3-21: 4204Cf Relay Module - Honeywell VISTA-128FBPN Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-128FBPN Installation and Setup Guide
DIP SWITCH:
WHITE AREAS DENOTE SWITCH HANDLES
ENABLES/DISABLES COVER TAMPER
ON = TAMPER DISABLED; OFF = TAMPER ENABLED
SHOWN DISABLED (AS SHIPPED).
DETERMINE 4204CF'S ADDRESS:
CONTROL'S INSTRUCTIONS SPECIFY ADDRESS TO
USE. "0" ADDRESS SETTING SHOWN (AS SHIPPED).
4204CF
DIP SWITCH
FOR SETTING DEVICE
ADDRESS AND
ENABLING/DISABLING TAMPER
COVER TAMPER (REED) SWITCH
4-PIN CONSOLE
PLUG
EITHER OR BOTH
CAN BE USED
TB1
13
14
15
16
YEL
DATA IN FROM CONTROL
BLK
GROUND
GRN
DATA OUT TO CONTROL
RED
12VDC; SUPPLIES POWER TO MODULE CIRCUITRY (INCLUDING APPLIANCE OUTPUT
RELAY COILS). CURRENT DRAIN AT 12V IS: 25mA + (80mA PER ACTIVE OUTPUT).
Installing 4101SN Relay Modules
The 4101SN V-Plex Single Output Relay Module is a serial number polling loop output device. The 4101SN features the
following:
The position of the relay is supervised, but not the actual external contact wiring.
Form C relay contacts rated at 2A, 28VAC/VDC with contact supervision.
One class B/style B EOLR-supervised auxiliary input zone.
Operating power and communication with control panels via the V-Plex polling loop.
Electronics mounted in a small plastic case with tamper-protected cover.
f Fire devices are used on the polling loop no more than 10 (ten) 4101SNs may be used.
NOTE: I
If are using ZONE # for the START of a polling loop output, and want the output to stop when the same zone
restores, the STOP programming must be blank.
No more than 20 polling loop outputs may be programmed for the same START or STOP condition in Output
Programming.
Connect the device to the polling loop, terminals 28 (+) and 29 (-). Be sure to observe polarity.

Installing a Remote Keyswitch

A UL-Listed remote keyswitch, such as the Honeywell 4146, can be used for remote arming/disarming of the burglary
part of the system and for silencing alarms. The keyswitch operates in only one particular partition.
The keyswitch is wired across zone 7. This zone is no longer available as a protection zone. Make sure *15 is assigned to
part (1-9). This sets zone 7 to response type 05.
Operation
A momentary short arms the partition in the AWAY mode, and a short held for more than 10 seconds arms the
partition in STAY mode 1. A subsequent short disarms the partition.
The keyswitch LEDs indicate the partition's status (see table that follows).
A momentary short silences Notification Appliance Circuits and keypad sounds, and disarms the system if it was
armed. A subsequent short clears the alarm memory indication and resets 2-wire smoke and glassbreak detectors (if
used).
The keyswitch can be used to silence fire alarms without disarming the burglary portion (program a "9" in field
15). A momentary short silences alarm outputs only if a fire alarm is present.
U L
In Commercial Fire installations, mount the keyswitch next to the primary keypad on keypad port 2 (J4 header) and
wire in conduit within the same room as the control panel. The keypad displays the UL-required "ALARM
SILENCED" when the keyswitch is used to silence a fire alarm.
3-22
OFF
POSITION 1
POSITIONS 2-5
TB2
12
NOTIFICATION
APPLIANCE
11
NC
OUTPUT B
10
NC
2K EOLR
9
EOL20
POLARIZED
8
NC
NOTIFICATION
7
NC
APPLIANCES
6
NOTIFICATION
APPLIANCE
5
OUTPUT A
4
2K EOLR
3
EOL20
2
NC
CONNECT TO A POWER-LIMITED 12V REGULATED
NC
1
UL1481 LISTED POWER SUPPLY.

Figure 3-21: 4204CF Relay Module

4204CF ADDRESS SETTINGS
SWITCH
ON
NUMBER
0
1
2
3
4
5
2
ON —
ON
ON
ON ON
ON ON —
3
4
ON ON ON ON
ON ON ON ON ON ON ON ON —
5
FOR UL COMMERCIAL FIRE INSTALLATIONS, ONLY ONE NOTIFICATION APPLIANCE
MODULE MAY BE USED, AND ONLY ONE NOTIFICATION APPLIANCE OUTPUT (A or B)
MAY BE USED ON THAT MODULE.
ALARM POLARITY SHOWN
EACH OUTPUT PROVIDES
STYLE Y SUPERVISION
EACH OUTPUT RATED 1.2A MAX
("—" means "OFF")
6
7
8
9
10
11
12
13
14
15
ON
ON
ON
ON
ON —
ON ON
ON ON
ON ON ON ON
NOTIFICATION APPLIANCE AND CONSOLE DATA
OUTPUTS ARE POWER-LIMITED.
ALL POWER-LIMITED WIRING MUST BE SEPARATED
FROM NON-POWER-LIMITED AND HIGH-VOLTAGE
WIRING BY 1/4" (6.4mm).
ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED
WHEN POWERED BY THE CONTROL PANEL.
NFPA-72 COMPLIANT.
4204CF-004-V1