Honeywell VISTA-128FBPN Installation And Setup Manual page 77

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

FIELD
TITLE and DATA ENTRIES
Auxiliary Input Alternate
3*19
Function Enable
0 = disable
1 = enable
Trigger Outputs Function
3*20
Selection
0 = remote keypad sounder
1 = keyswitch LEDs
Field 3*19 = 0
J2 Pin
1
2
3
Burglary Alarm
4
Fire Supervisory
5
Remote Console
6
7
8
9
Communicator Xmit Okay
Maximum Number of Dialer
3*21
Attempts
Enter the number of dialing attempts 1-8.
Dialer Selection
3*30
0 = disable
1 = enable
Backup Dialer TouchTone or
3*31
Rotary
0 = rotary
1 = touchtone
Zone Type Restore Enables for
3*50
Types 16-18
0 = disable
1 = enable
Reset on Second OFF for Bell 1
3*55
0 = disable
1 = enable
Reset on Second OFF for Bell 2
3*56
0 = disable
1 = enable
Confirmation of Arming Ding Bell
3*57
2 & Auxiliary Relay
0 = disable
1 = enable
Field 3*19 = 0
Field3*20 = 0
Panic Alarm
Trouble
Burglary Alarm
Fire Supervisory
Fire Alarm
Keyswitch Ready LED
Sounder
Open/Close
Keyswitch Armed LED
Ground
Communicator Xmit Okay
EXPLANATION
If enabled, pins 5 and 9 on the J2 connector function as RS232 output and
input, respectively. If disabled, they function as fire alarm trigger and
communications device Xmit Okay. See the chart at field 3*20 for the J2
trigger configurations.
NOTE: If field 3*19 is enabled, you cannot use a communications device
connected to the J2 trigger.
Select the function of the J2 trigger outputs. See chart below.
Field3*20 = 1
Panic Alarm
Trouble
Fire Alarm
Ground
Select the maximum number of dialer attempts for the system.
NOTE: Must be 3, 4, or 5 for NFPA 72 compliant systems if a secondary
phone number is programmed.
This field has two entries, one for each dialer (main and backup). Enter 1 if the
dialer is being used.
NOTE: If 3*30 is disabled (0, 0), the panel does not report at all via
communications device.
Select the dialing method for the backup dialer.
This field has three entries, one for each zone type. Select the zone types that
will send Restore reports.
Must be 1 for UL commercial fire and burglary installations
If enabled, the system silences bell 1 output when the second User Code +
OFF Code is entered after a fire alarm. If disabled, the system silences bell 1
output after the first User Code + OFF.
If enabled, the system silences bell 2 output when the second User Code +
OFF Code is entered after a fire alarm. If disabled, the system silences bell 2
output after the first User Code + OFF.
This field has two entries, one for bell 2 and one for the auxiliary relay. If
enabled, produces ½-second external alarm sounding ("ding") at the end of
exit delay (or after kissoff from the central station, if sending closing reports).
NOTE: If using a keyfob, when the button is pressed, either for arming or
disarming, the bell will ding indicating that the button is working.
Must be 1 for Commercial Burglary installations.
Section 5 – Data Field Descriptions
Field 3*19 = 1
As selected in field 3*20
As selected in field 3*20
As selected in field 3*20
As selected in field 3*20
RS232 Output
As selected in field 3*20
As selected in field 3*20
Ground
RS232 Input
5-15