Program Modes

There are two programming modes for the VISTA-
128FBPN. These are the Data Field Program Mode and
the #93 Menu Mode. The Data Field Program Mode is
where many system options are programmed. The #93
Menu Mode is an interactive mode that require a 2-line
alpha keypad (6160/6160CR-2).

Entering and Exiting Programming Mode

Enter Programming mode entering the Installer Code
+ [8] + [0] + [0] + [0] keys once the power has been
applied to the control. The factory installer code can be
changed once in the Program mode (field ✳00).
NOTE: The default for the Installer Code is 5140.

Data Field Programming Mode

In the Data Field Program Mode you may access any
field simply by entering either [✳] or [#] + the field
number:
To write or change information in a field press [✳]
+ the field number (✳03).
To read the information in a field press [#] + the
field number (#03).
When the entries for a field are completed, the keypad
beeps three times and advances to the next field.
SUMMARY OF DATA FIELD PROGRAMMING
COMMANDS
✳91
Select partition for programming partition-specific fields
✳92
Display the software revision level of the control panel
✳93
Enter Menu mode programming
✳94
Go to next page of fields
✳99
Go back to previous page of fields or exit Programming
Mode with no installer code lockout
✳98
Exit Programming Mode with Installer Code lockout
Moving from One Page of Programming to Another
The data fields are grouped into three levels (referred to
as "pages"). The first page is accessed as soon as
Programming Mode is entered.
The second and third pages of data fields are indicated
at the keypad by a 1 and 2, respectively, in front of the
2-digit field address. "ALT PROGRAM MODE" is
S E C T I O N
Programming
The factory-loaded defaults (✳97) enable
keypad addresses 00-01 only. A keypad set to
one of these addresses must be used to
program the system initially.
Exit the Programming mode by either method a or b:
a.
Press [✳] + [9] + [8]. Exiting by this method
prevents the installer code from being used to re-
enter Programming mode. The only way to re-
access programming mode is by depressing both the
[✱] and [#] keys at the same time within 30 seconds
of power-up.
b.
Press [✳] + [9] + [9]. Exiting by this method
permits the installer code to be being used to re-
enter Programming mode.
displayed along with a "100", "200" or "300," indicating
which page of program fields is accessed.
To access the next level of programming fields:
Press ✳94.
1
2
Press [✳] + [XX], where XX = the last two digits of
the program field, and make the desired entry.
NOTES:
Press ✳94 to move to 2
nd
press ✳99 to move back to 1
Press ✳94 to move to 3
rd
press ✳99 to move back to 2
Press ✳94 to move to 4
th
press ✳99 to move back to 3
Entry Errors
If an address is improperly entered, the keypad
displays "Not Used" or "FC."
If a program entry is improperly entered (for
example, a larger number than is permitted), the
keypad display will go blank.
In either of the above cases, simply re-enter [✳] + the
correct field number and then enter the correct data.
Programming System-Wide Data Fields
Values for some programming fields are system-wide
(global), and some can be different for each partition
(partition-specific).
4
page, (fields 1✳01 - 1✳76);
st
page.
page (fields 2✳00 - 2✳88);
nd
page.
page, (fields 3✳00 - 3✳85);
rd
page.
4-1