Honeywell VISTA-128FBPN Installation And Setup Manual page 74

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-128FBPN Installation and Setup Guide
FIELD
TITLE and DATA ENTRIES
Control Relay (partition-specific)
1*76
01-96 = relay number
00 = relay not used.
st
Log 1
Main Signal
1*77
0 = disable
1 = enable
Extended Home Control Events
1*78
0 = limited
1 = extended
Home Control Events
1*79
0 = disable
1 = enable
Log Faults & Restores
1*80
0 = disable
1 = enable
Number of Partitions
2*00
Enter 1-8.
Daylight Saving Time Start/End
2*01
Month
0 = disable
1 = enable
Daylight Saving Time Start/End
2*02
Weekend
0 = disable
1 = enable
Auto-Arm Delay (partition-
2*05
specific)
00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto arming.
Auto-Arm Warning Period
2*06
(partition-specific)
01-15 times 1-minute warning.
00 = no warning period.
Auto-Disarm Delay (partition-
2*07
specific)
00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto disarming.
Force Arm Enable for Auto-Arm
2*08
(partition-specific)
0 = disable
1 = enable
5-12
EXPLANATION
If enabled, the assigned relay closes for 2 seconds when the user enters his
code and presses 0.
Must be set to "00" for Commercial Fire and Burglary installations.
NOTE: See SECTION 3: Installing the Control for enhanced access control
capabilities.
If enabled, the system logs the first maintenance signal from each smoke
detector. If disabled, no logging occurs.
If extended, there are 255 commands to the home control command set. If
limited, there are 32 commands to the home control command set.
Home Control Automation is not allowed in UL installations.
Select the type of events (status reports) transmitted via the RS232 output.
Home Control Automation is not allowed in UL installations.
When enabled automatically transfers data of the RS232 output.
Home Control Automation is not allowed in UL installations.
Enter the number of partitions used in the system.
Enter the months (00-12) in which daylight saving time starts and ends.
Enter 00, 00 if daylight saving time does not apply to the user's region.
Standard setting for U.S. is 03, 11.
Enter the start and end weekends for daylight saving time as follows: 1=first;
2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from last.
Standard setting for U.S. is 2, 1.
This is the time between the end of the arming window and the start of auto-
arm warning time (field 2*06).
NOTE: This field must be set to "00" for UL installations.
This is the time that the user is warned by a keypad sounding and display to
exit the premises prior to auto arming of the system.
NOTE: This field must be set to "00" for UL installations.
This is the time between the end of the disarming window and the start of auto
disarming of the system.
NOTE: This field must be set to "15" for UL864 compliance.
If enabled, the system automatically bypasses any faulted zones when it
attempts to auto-arm.
If disabled, the system does not auto-arm.
NOTE: Force arm is not approved for ULC applications.
NOTE: This field must be set to "0" for UL installations.