This section describes the procedures for mounting and wiring the control panel and all the peripheral devices.

Mounting the Control Cabinet

To mount the control cabinet, perform the following steps:
Step
Action
1
Before mounting the circuit board, remove the metal knockouts for the wiring entry that you will be using.
DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN
INSTALLED.
2
Using fasteners or anchors (not supplied), mount the control cabinet to a sturdy wall in a clean, dry area
that is not readily accessible to the general public. The back of the cabinet has 4 holes for this purpose.
To provide certificated burglary service for UL installations, refer to the special requirements and Figure 3-2. Cabinet
U L
Attack Resistance Considerations to follow.

Installing the Cabinet Lock

To install the lock, see Figure 3-1 and perform the
following steps:
Step
Action
1
Remove cabinet door, then remove the lock
knockout from the door. Insert the key into the
lock.
2
Position the lock in the hole, making certain
that the latch will make contact with the latch
bracket when the door is closed.
3
When correctly positioned, insert supplied lock
clip on the inside of the cabinet into the slots
on the lock cylinder. Use ADEMCO Lock #
N6277V1 and Lock Clip # P3422-2 (supplied).

Mercantile Premises Listing Guidelines

The panel door must be supervised. Mount the
clip-on tamper switch (supplied) to the cabinet's
right side wall and wire it to zone 6.
Assign zone 6 to a burglary partition. Program it
for day trouble/night alarm (zone type 5) when only
one burglary partition is used. Program it for 24-
hr. audible alarm (zone type 7) when more than one
burglary partition is used. Enable field 3*17 so
that the system responds to a ground fault in
accordance with its zone type rather than a ground
fault response.
24-Hour audible alarm (zone types 6 and 7) is
ULC
not approved for ULC applications.
S E C T I O N
Installing the Control
CHECK
POSITION
LOCKED
PUSH
UNLOCKED
CABINET DOOR
BOTTOM

Figure 3-1: Installing the Lock

All wiring between the transformer and panel must
be run in conduit. Remaining wires do not need to
be run in conduit.
All unused knockouts must be plugged using the
disc plugs and carriage bolts (supplied), as
indicated in Figure 3-2.
Fasten the cabinet door to the cabinet backbox
using the 15 one-inch-long Phillips-head screws
(supplied) after all wiring, programming, and
checkout procedures have been completed.
3
PUSH
ON LOCK
UNTIL IT
SNAP
IS SEATED
TAB
SECURELY
SNAP
TAB
STEP 1
STEP 2
3-1