Ignore Expansion Zone Tamper; Intelligent Test Report; Test Report Interval - Honeywell VISTA-128FBPN Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

FIELD
TITLE and DATA ENTRIES
Randomize AC Loss Report
*19
0 = within 2 minutes
1 = 10-40 minutes
2 = 1-3 hours
3 = 6-12 hours without Type 13, 1-3 hours
with Type 13
VIP Module Phone Code
*20
1-9 = first digit of access code
∗ ∗ ∗ ∗ or # = second digit of access code (enter #
+11 for "∗", or # +12 for "#")
To disable enter 00 for the 1
Keypad Panic Enables (partition-
*22
specific)
0 = disable
1 = enable

Ignore Expansion Zone Tamper

*24
0 = disable (tamper detection)
1 = enable (no tamper detection)
Burglary Trigger for Response
*25
Type 8
0 = disable
1 = enable

Intelligent Test Report

*26
0 = disable
1 = enable

Test Report Interval

*27
Enter 0001-9999 for the test report interval in
hours.
Enter 0000 for test reporting.
Power-Up in Previous State
*28
0 = disable
1 = enable
Quick Arm (partition-specific)
*29
0 = disable
1 = enable
EXPLANATION
If enabled, randomizes AC loss reporting within the selected time after an
actual AC loss.
If disabled (0), AC loss reporting about 2 minutes after actual AC loss.
Selecting this option helps prevent an overload of AC loss messages at the
central station during a community blackout.
Must be 2 for Commercial Fire installations.
If a 4286 Voice Module is being used, enter the 2-digit phone code used to
access the system.
Must be set to "00" for Commercial Fire and Commercial Burglary
installations.
st
digit
If enabled, the keypad panics (zones 995, 996, and 999) may be used in this
partition. There are three entries in this field, one for each panic.
Use for Burglary panic types only.
Do not use on partition 1 on fire systems.
If disabled, the system monitors the tampers on expansion zones.
NOTE: Only applicable to certain polling loop sensors with tamper switches or
5800 Series transmitters.
Must be 0 for UL installations.
If enabled, allows triggering of the voltage output 3 on Pin 3 of the J2 header
to include zone response type 8 (24-hr. auxiliary).
If enabled, no test report is sent if any other type of report was sent since the
last test report.
If disabled, test reports are sent at the set intervals, regardless of whether or
not any other report has been sent.
Must be 0 for Commercial Fire and UL Commercial Burglary installations.
If a test report is desired, enter a test code in Report Code Programming in
#93 Menu Mode. Set first test report time in field *83.
Maximum Test report interval is 0024 for Commercial Fire and Commercial
Burglary installations.
If enabled, the system, upon power-up, reverts to its status prior to a complete
power loss.
If disabled, the system always powers up in a disarmed state.
NOTES:
Neither authority level 0 nor 5 can be used to disarm the system if the control
powers up armed.
When Power Up in Previous State is enabled, if the panel powers up armed, it
may take up to 3 minutes before an alarm is recognized and initiated.
Must be 1 for UL applications.
If enabled, allows arming of the burglary system in AWAY, STAY, INSTANT,
or MAXIMUM mode by using the [#] key instead of the user code.
NOTES:
When armed, the system reports closing as User 0 if Open/Close reporting for
User #2 (typically a Master level user) was enabled for a given partition.
If Quick Arm is used, the Installer Code and Authority Level 5 codes cannot
disarm the system.