Honeywell VISTA-128FBPN Installation And Setup Manual page 73

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

FIELD
TITLE and DATA ENTRIES
Disable Download Callback
1*53
0 = callback required
1 = no callback required
European Date Format
1*55
0 = disable (mm/dd/yy)
1 = enable (dd/mm/yy)
AC 60Hz or 50Hz
1*56
0 = 60Hz
1 = 50Hz
Enable 5800 RF Button Global
1*57
Arm
0 = disable
1 = enable
Enable 5800 RF Button Force
1*58
Arm
0 = disable
1 = enable
Zone 5 Audio Alarm Verification
1*60
0 = disable
1 = enable
Abort Verify
1*61
0 = disable
1 = enable
Event Log Types
1*70
0 = disable
1 = enable
12/24 Hour Type Stamp Format
1*71
0 = 12-hour
1 = 24-hour
Event Log Printer On-Line Mode
1*72
0 = disable
1 = enable
Printer Baud Rate
1*73
0 = 1200
1 = 300
Relay Timeout XXX Minutes
1*74
Enter 000-127 times 2 minutes (000-254).
Relay Timeout YYY Seconds
1*75
Enter 000-127 seconds.
EXPLANATION
Select whether a callback from the control panel is required for downloading.
Must be set to "0" for Commercial Fire and Burglary installations.
Select the date format for display in the event log.
Select the frequency for the AC.
Must be set to 0 for U.S. and Canadian installations.
If enabled, the system arms/disarms in accordance with the button's user's
global arming settings.
Must be 0 for Commercial Fire and Commercial Burglary installations.
If enabled, allows the RF button user to force a bypass of all faulted zones
when arming the system.
NOTE: When attempting to arm the system, the keypad beeps once after the
button is pressed if any faulted zones are present. The user should then
press the button again within 4 seconds to force-bypass those zones and arm
the system.
NOTE: Force Arm is not approved for ULC applications.
If enabled, zone 5 is used for 2-way audio (AAV).
Must be set to "0" for UL commercial fire and burglary installations.
NOTE: Zone 5 cannot be used as protection zone.
If enabled and an alarm occurs on a non-fire zone, the system displays
"ALARM ABORTED", if a user enters the code + off sequence during the
Abort Window (field *88).
This field has five entries as follows: Alarm, Check, Bypass, Open/Close, and
System. If enabled, the system logs those events into the event log.
Select the type of time stamping for the event log.
If enabled, the system prints the events as they occur.
If disabled, the system prints the log only upon request.
Select the baud rate for the serial printer.
This is used for #80 Menu Mode Time-Driven event relay command numbers
"04/09" and Output Programming in the #93 Menu Mode Programming output
command "56."
This is used for #80 Menu Mode Time-Driven event relay command numbers
"05/10" and Output Programming in the #93 Menu Mode Programming
command "57."
Section 5 – Data Field Descriptions
5-11