Zone Number Designations - Honeywell VISTA-128FBPN Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-128FBPN Installation and Setup Guide
MAIN MENU
SCHEDULED CHK-IN
1 = YES 0 = NO
0
Following is a list of commands used while in the Menu Mode:
#93
Enters Menu Mode.
[✳]
Serves as [ENTER] key. Press to have keypad accept entry.
[#]
Backs up to previous screen.
0
Press to answer NO.
1
Press to answer YES.
00, or 000+[✳]
Quits Menu Mode and goes back to Data Field Programming Mode, if entered at first prompt of each main menu option.

Zone Number Designations

The VISTA-128FBPN supports up to 128 zones of
hardwire, polling loop and/or wireless protection,
distributed among up to 8 partitions. The following
table lists the zone numbers and the types of sensors
that can be used with each, and some alternate
functions of the zones.
Zone
Function
1 & 2
2-wire Smoke Detectors (if used)
6
Cabinet Tamper/Ground Fault (if used)
7
Keyswitch (if used)
8
Latching-Type Glassbreak Detectors (if used)
1-8
Traditional Hardwired Zones
1-128
5800 Series Wireless Devices
9-128
Polling Loop Devices
✳ + 1 Panic (Do not use in Fire Alarm applications)
995
996
# + 3 Panic (Do not use in Fire Alarm applications)
✳ + # Panic (Do not use in Fire Alarm applications)
999
Zone Defaults
Zone #
Zone Type
001
09
002
09
003
03
004
03
005
03
006
03
007
03
008
03
009–128
00
601-632
00
NOTES:
* Zone 992 is the Duress zone. Programming of the zone
response type is not applicable. This zone requires only the
report code programming.
4-4
OPTIONS
For defining the schedule for the system to automatically call the downloader.
#93 Menu Mode Programming Commands
Zone #
Zone Type
800-830
00
970
19
971-974
19
975
00
988 & 990
00
992*
N/A
995
00
996
00
997
19
999
06
Zone Index
The zones are designated as follows:
ZONE #
ZONE
RANGE
FUNCTION
001 – 128
Protection
zones
601 – 632
Relay
Supervision
Zones
800 – 830
ECP Device
Supervision
Zones
970-977,
System
988, 990, &
Supervision
997
Zones
992, 995 –
Duress and
999
Keypad Panics
Supervision zones should be given a response type of either 05
(Trouble by Day, Alarm by Night) or 19 (24-Hour Trouble).
ACTUAL ZONE
As indicated
6 + 2-digit Relay Number; e.g.,
Relay Number 03, if supervised,
is zone 603.
NOTE: Relay supervision
should be used only for
relays on 4204CF modules.
8 + 2-digit Device Address; e.g.,
Device Address 01, if
supervised, is zone 801.
970:
Bell 1Output
971
Bell 2 Output
972
Earth Ground
973
J2 Input 1
communications
(
device
)
974
Dialer 1
975
Dialer 2
976
Auxiliary Relay
977
J2 Trigger Outputs
nd
988:
2
Wireless Receiver –
not receiving signals
st
990:
1
Wireless Receiver –
not receiving signals
997:
Polling Loop (short
circuit)
992:
Duress
1 + ✳ panic (A key)
995:
996:
3 + # panic (C key)
✳ + # panic (B key)
999: