Output Relay Settings; Text Settings - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

CHAPTER 1: GETTING STARTED
1.3.5

Output Relay Settings

1.3.6

Text Settings

469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Output relays (Trip or Alarm) can be associated to the Auxiliary Relays 2 and 3. Each can be
selected individually, or in combination, in response to customer specific requirements,
which can be initiated by any protection element or function, whose
settings has them selected.
 Select the
RELAYS
If an application requires the short circuit protection element to operate the Auxiliary
Output 3 relay,
 Select this output relay by pressing the value key until the desired
combination appear in the display.
 Press the
As before, confirmation of this action will momentarily flash on the
display.
Text settings have data values which are fixed in length but user-defined in character. They
may be composed of uppercase letters, lowercase letters, numerals, and a selection of
special characters. The editing and storing of a text value is accomplished using the
decimal [.],
, and
VALUE
ENTER
For example:
 Move to message
INPUT 1 FUNCTION
Sw. A".
The relay will display the following message:
 Press the
The name of this user-defined input will be changed in this example
from the generic "General Sw. A" to something more descriptive.
If an application is to be using the relay as a station monitor, it is more informative to
rename this input "Station Monitor".
S6 CURRENT ELEM.  SHORT CIRCUIT TRIP  ASSIGN TRIP
settings message.
ASSIGN TRIP RELAYS:
Trip
ASSIGN TRIP RELAYS:
Trip & Auxiliary3
key to store this change into memory.
ENTER
NEW SETPOINT HAS
BEEN STORED
keys.
S3 DIGITAL INPUTS  ASSIGNABLE INPUT 1 
, and scrolling with the
INPUT 1 FUNCTION:
General Sw. A
 key to view the next settings,
MESSAGE
ASSIGN RELAYS
keys, select "General
VALUE
SWITCH NAME
1–15
.