5.14.2 Pre-Fault Setup
PRE-FAULT
SETUP
5–102
PATH: SETTINGS
S13 469 TESTING
[]
PRE-FAULT CURRENT
PHASE A: 0.00 x CT
PRE-FAULT CURRENT
MESSAGE
PHASE B: 0.00 x CT
PRE-FAULT CURRENT
MESSAGE
PHASE C: 0.00 x CT
PRE-FAULT GROUND
MESSAGE
CURRENT: 0.0 A
PRE-FAULT VOLTAGES
MESSAGE
VLINE: 1.00 x RATED
PRE-FAULT CURRENT
MESSAGE
LAGS VOLTAGE: 0°
PRE-FAULT DIFF AMPS
MESSAGE
IDIFF: 0.00 x CT
PRE-FAULT STATOR
MESSAGE
RTD TEMP: 40°C
PRE-FAULT BEARING
MESSAGE
RTD TEMP: 40°C
PRE-FAULT OTHER
MESSAGE
RTD TEMP: 40°C
PRE-FAULT AMBIENT
MESSAGE
RTD TEMP: 40°C
PRE-FAULT SYSTEM
MESSAGE
FREQUENCY: 60.0 Hz
PRE-FAULT ANALOG
MESSAGE
INPUT 1: 0%
PRE-FAULT ANALOG
MESSAGE
INPUT 2: 0%
PRE-FAULT ANALOG
MESSAGE
INPUT 3: 0%
PRE-FAULT ANALOG
MESSAGE
INPUT 4: 0%
The values entered under Pre-Fault Values will be substituted for the measured values in
the 469 when the simulation mode is "Simulate Pre-Fault".
PRE-FAULT SETUP
Range: 0.00 to 20.00 x CT in steps of
Range: 0.00 to 20.00 x CT in steps of
Range: 0.00 to 20.00 x CT in steps of
Range: 0.0 to 5000.0 A in steps of 0.1
Range: 0.00 to 1.10 x RATED in steps of
Range: 0 to 359° in steps of 1
Range: 0.00 to 1.10 x RATED in steps of
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: 45.0 to 70.0 Hz in steps of 0.1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
0.01
0.01
0.01
0.01
0.01