Clear Data - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

5.2.7

Clear Data

 CLEAR DATA []
5.2.8
Installation
 INSTALLATION
5–16
PATH: SETTINGS
S1 469 SETUP
CLEAR LAST TRIP
DATA: No
RESET MWh and Mvarh
MESSAGE
METERS: No
CLEAR PEAK DEMAND
MESSAGE
DATA: No
CLEAR RTD
MESSAGE
MAXIMUMS: No
CLEAR ANALOG I/P
MESSAGE
MIN/MAX: No
CLEAR TRIP
MESSAGE
COUNTERS: No
PRESET DIGITAL
MESSAGE
COUNTER: No
CLEAR EVENT
MESSAGE
RECORDER: No
These commands may be used to clear various historical data.
CLEAR LAST TRIP DATA: Clears the last trip data.
RESET MWh and Mvarh METERS: Resets the MWh and Mvarh metering to zero.
CLEAR PEAK DEMAND DATA: Clears the peak demand values.
CLEAR RTD MAXIMUMS: All maximum RTD temperature measurements are stored
and updated each time a new maximum temperature is established. This command
clears the maximum values.
CLEAR ANALOG I/P MIN/MAX: The minimum and maximum analog input values are
stored for each analog input. These minimum and maximum values may be cleared at
any time.
CLEAR TRIP COUNTERS: There are counters for each possible type of trip. This
command clears these counters.
PRESET DIGITAL COUNTER: When one of the assignable Digital Inputs is configured as
"Counter", this command presets the counter. If the counter is an incrementing type,
setting the preset value to "0" effectively resets the counter.
CLEAR EVENT RECORDER: The event recorder saves the last 256 events,
automatically overwriting the oldest event. If desired, this command can clear all
events to prevent confusion with old information.
PATH: SETTINGS
S1 469 SETUP
[]

CLEAR DATA

INSTALLATION
RESET MOTOR
INFORMATION: No
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes