CHAPTER 5: SETTINGS
5.11.2 Power Factor
 POWER
FACTOR
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL

PATH: SETTINGS
S10 POWER ELEMENTS
[]
BLOCK PF ELEMENT
FROM START: 1 s
POWER FACTOR
MESSAGE
ALARM: Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
POWER FACTOR LEAD
MESSAGE
ALARM LEVEL: Off
POWER FACTOR LAG
MESSAGE
ALARM LEVEL: Off
POWER FACTOR ALARM
MESSAGE
DELAY: 1.0 s
POWER FACTOR ALARM
MESSAGE
EVENTS: Off
POWER FACTOR
MESSAGE
TRIP: Off
ASSIGN TRIP RELAYS:
MESSAGE
Trip
POWER FACTOR LEAD
MESSAGE
TRIP LEVEL: Off
POWER FACTOR LAG
MESSAGE
TRIP LEVEL: Off
POWER FACTOR TRIP
MESSAGE
DELAY: 1.0 s
If the 469 is applied on a synchronous motor, it is desirable not to trip or alarm on power
factor until the field has been applied. Therefore, this feature can be blocked until the
motor comes up to speed and the field is applied. From that point forward, the power
factor trip and alarm elements will be active. Once the power factor is less than either the
Lead or Lag level, for the specified delay, a trip or alarm will occur indicating a Lead or Lag
condition. The power factor alarm can be used to detect loss of excitation and out of step.
The 469 is not designed to estimate power factor when both of the following conditions
are true:
• setpoint System Nominal Frequency is "Variable"
• Input Voltage is not at frequency 60 Hz.
POWER FACTOR
Range: 0 to 5000 s in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
Range: 0.05 to 1.00 in steps of 0.01.
Enter 1.00 to turn feature off.
Range: 0.05 to 1.00 in steps of 0.01.
Enter 1.00 to turn feature off.
Range: 0.2 to 30.0 s in steps of 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 0.05 to 1.00 in steps of 0.01.
Enter 1.00 to turn feature off.
Range: 0.05 to 1.00 in steps of 0.01.
Enter 1.00 to turn feature off.
Range: 0.2 to 30.0 s in steps of 0.1
5–83