D Igital I Nputs - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

6.2.4
Start Blocks
 START BLOCKS
6.2.5
Digital Inputs
 DIGITAL
INPUTS
6–8
If the 469 chassis is only partially engaged with the case, the
service alarm appears after 1 second. Secure the chassis handle to ensure that
PROPERLY
all contacts mate properly.
PATH: ACTUAL VALUES
A1 STATUS
[]
NO START BLOCKS
ACTIVE
OVERLOAD LOCKOUT
MESSAGE
BLOCK: 25 min.
START INHIBIT BLOCK
MESSAGE
LOCKOUT TIME: 20 min.
STARTS/HOUR BLOCK
MESSAGE
LOCKOUT TIME: 20 min.
TIME BETWEEN STARTS
MESSAGE
LOCKOUT TIME: 20 min.
RESTART BLOCK
MESSAGE
LOCKOUT: 1200 s
WARNING
MESSAGE
469 NOT PROGRAMMED
Any active blocking functions may be viewed here. The
message is seen only if the Phase CT Primary or Motor FLA settings have not been
programmed.
PATH: ACTUAL VALUES
A1 STATUS
[]
ACCESS
SWITCH STATE: Open
TEST
MESSAGE
SWITCH STATE: Open
STARTER STATUS
MESSAGE
SWITCH STATE: Open
EMERGENCY RESTART
MESSAGE
SWITCH STATE: Open
REMOTE RESET
MESSAGE
SWITCH STATE: Open
ASSIGNABLE DIGITAL
MESSAGE
INPUT1 STATE: Open
ASSIGNABLE DIGITAL
MESSAGE
INPUT2 STATE: Open
CHAPTER 6: ACTUAL VALUES

START BLOCKS
Range: N/A. Message seen when no
Note: Message seen only after an
Range: 0 to 500 min.
Range: 0 to 60 min.
Range: 0 to 500 min.
Range: 0 to 50000 sec.
Note: Seen only if Phase CT Primary
WARNING 469 NOT PROGRAMMED

DIGITAL INPUTS
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
ALARM, 469 NOT INSERTED
start blocks are active
overload trip
or Motor FLA not programmed