GE 469 Instruction Manual page 174

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

 ASSIGNABLE []
INPUT 1
 ASSIGNABLE []
INPUT 1
5–30
Pressure Switch Alarm

PATH: SETTINGS
S3 DIGITAL INPUTS
INPUT 1 FUNCTION:
Pressure Sw Alarm
BLOCK PRES. SW. ALARM
MESSAGE
FROM START: 0 s
PRESSURE SWITCH
MESSAGE
ALARM: Unlatched
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
PRESSURE SW. ALARM
MESSAGE
DELAY: 5.0 s
PRESSURE SW. ALARM
MESSAGE
EVENTS: Off
These settings apply only if the
Once the pressure switch alarm function is chosen for one of the assignable digital inputs,
the settings messages shown here will follow the assignment message. The Pressure
Switch alarm feature may be blocked for a specified period of time from a motor start. A
value of zero for the block time indicates that the feature is always active, when the motor
is stopped or running. After the block delay has expired, the digital input will be monitored.
If a closure occurs, after the specified delay, an alarm will occur.
Pressure Switch Trip

PATH: SETTINGS
S3 DIGITAL INPUTS
INPUT 1 FUNCTION:
Pressure Switch Trip
BLOCK PRES. SW. TRIP
MESSAGE
FROM START: 0 s
ASSIGN TRIP RELAYS:
MESSAGE
Trip
PRESSURE SW. TRIP
MESSAGE
DELAY: 5.0 s
These settings apply only if the
Once the Pressure Switch Trip function is chosen for one of the digital inputs, the settings
messages shown here will follow the assignment message. The Pressure Switch Trip
feature may be blocked for a specified period of time from a motor start. A value of zero for
the Block time indicates that the feature is always active, when the motor is stopped or
running. After the block delay has expired, the digital input will be monitored. If a closure
occurs, after the specified delay, a trip will occur.

ASSIGNABLE INPUT 1(4)
Range: See above
Range: 0 to 5000 s in steps of 1
Range: Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Range: 0.1 to 100.0 sec., step: 0.1
Range: On, Off
is "Pressure Sw. Alarm".
INPUT 1(4) FUNCTION

ASSIGNABLE INPUT 1(4)
Range: See above
Range: 0 to 5000 sec.; step: 1
Range: Trip, Trip & Auxiliary2, Trip &
Range: 0.1 to 100.0 s in steps of 0.1
is "Pressure Switch Trip".
INPUT 1(4) FUNCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Alarm & Auxiliary2 & Aux3,
Alarm & Auxiliary3, Auxiliary2,
Aux2 & Aux3, Auxiliary3, None
Aux2 & Aux3, Trip & Auxiliary3