CHAPTER 2: INTRODUCTION
.
FIGURE 2–1: Single Line Diagram
Typical applications include: pumps, fans, compressors, mills, shredders, extruders,
debarkers, refiners, cranes, conveyors, chillers, crushers, and blowers.
Some of the protection highlights are detailed here; a complete list is shown below. Four
assignable digital inputs may be configured for a number of different features including
tachometer or generic trip and alarm with a programmable name. The thermal model
incorporates unbalance biasing, RTD feedback, and exponential cooling. In addition to the
15 standard overload curves, there is a custom curve feature and a curve specifically
designed for the starting of high inertia loads, when the acceleration time exceeds the safe
stall time. A second overload curve is provided for two-speed motors. Ground faults or
earth leakage as low as 0.25 A may be detected using the GE Grid Solutions 50:0.025
Ground CT. CT inputs for phase differential protection are also provided. The 12 RTD inputs
provided may be individually field programmed for different RTD types. Voltage
transformer inputs allow for numerous protection features based on voltage and power
quantities. Four 4 to 20 mA analog inputs may be used for tripping and alarming on any
transducer input such as vibration, pressure, flow, etc.
2–2
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL