S Tarter S Tatus - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
5.4.2
Starter Status
 STARTER
STATUS
5.4.3
Assignable Inputs 1(4)
 ASSIGNABLE []
 ASSIGNABLE []
 ASSIGNABLE []
 ASSIGNABLE []
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Remote Reset
Shorting terminals D18 and D23 resets any trips or latched alarms provided that the
condition that caused the alarm or trip is no longer present. If there is a lockout time the
Block Start relay will not reset until the lockout time has expired.

PATH: SETTINGS
S3 DIGITAL INPUTS
[]
This input is necessary for all motors. The 469 determines that a motor has stopped when
the phase current falls below the level that the relay can measure (5% of CT primary).
Monitoring an auxiliary contact from the breaker or contactor prevents the relay from
detecting additional starts when an unloaded motor is loaded, or issuing a block start after
an unloaded motor is started and running at less than 5% CT rated primary current.
If "Starter Auxiliary A" is chosen, terminals D16 and D23 are monitored to detect the
breaker or contactor state, open signifying the breaker or contactor is open and shorted
signifying closed. The 469 will then determine that a motor has made the transition from
'running' to 'stopped' only when the measured current is less than 5% CT ratio and the 'a'
contact is open.
If "Starter Auxiliary B" is chosen, terminals D16 and D23 are monitored to detect the
breaker or contactor state, open signifying the breaker or contactor is closed and shorted
signifying open. The 469 then determines that a motor has made the transition from
'running' to 'stopped' only when the measured current is less than 5% CT ratio and the 'b'
contact is closed.
Main Menu

PATH: SETTINGS
S3 DIGITAL INPUTS
INPUT 1
INPUT 2
INPUT 3
INPUT 4
STARTER STATUS
STARTER STATUS SW:
Starter Auxiliary A

ASSIGNABLE INPUT 1(4)
INPUT 1 FUNCTION:
Off
INPUT 2 FUNCTION:
Off
INPUT 3 FUNCTION:
Off
INPUT 4 FUNCTION:
Off
Range: Starter Auxiliary A,
Starter Auxiliary B
Range: see below
Range: see below
Range: see below
Range: see below
5–27