CHAPTER 4: INTERFACES
4.1.9

Flash Messages

469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Message
Self-Test Warning 10
Schedule Maintenance
Clock Not Set
Program Date/Time
Unit Temp. Exceeded
Service/CheckAmbient
Unit Not Calibrated
Replace Immediately
Relay Not Configured
Consult User Manual
Service Required
Schedule Maintenance
Flash messages are warning, error, or general information messages displayed in response
to certain key presses. The length of time these messages remain displayed can be
programmed in
S1 RELAY SETUP
factory default flash message time is 4 seconds. For additional information and a complete
list of flash messages, refer to Flash Messages on page 6–38 .
Table 4–1: Self-Test Warnings
Severity
Occurs if factory data was not set or was lost.
Maintenance
Factory data includes: serial number, calibration
Alert
date, and order code.
Minor
Occurs if the clock has not been set.
Caused by the detection of unacceptably low (less
Minor
than -40°C) or high (greater than +85°C)
temperatures detected inside the unit.
This warning occurs when the relay has not been
Minor
factory calibrated.
This warning occurs when the 469 CT Primary or
Minor
FLA is set to "None".
Caused by a failure of the real time clock circuit.
Minor
The ability of the relay to maintain the current
date and time is lost.


PREFERENCES
DEFAULT MESSAGE CYCLE TIME
Failure description
. The
4–9