CHAPTER 7: TESTING
0%
25%
50%
75%
100%
0%
25%
50%
75%
100%
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
ANALOG
EXPECTE
OUTPUT
D
FORCE
AMMETE
VALUE
R
READING
4 mA
8 mA
12 mA
16 mA
20 mA
0 to 1 mA Analog Input
 Alter the following settings:

S12 ANALOG I/O

S12 ANALOG I/O

S12 ANALOG I/O
Analog Inputs 2 to 4)
Analog output values should be ±0.01 mA on the ammeter. Measured analog input
values should be ±10 units.
 Force the analog outputs using the following settings:

S13 TESTING
TEST ANALOG OUTPUT
"Enabled"

S13 TESTING
TEST ANALOG OUTPUT
(enter desired percent, repeats for analog output 2-4)
 Verify the ammeter readings as well as the measured analog input
 View the measured values in:
ANALOG
EXPECT
OUTPUT
ED
FORCE
AMMETE
VALUE
R
READIN
G
0 mA
0.25 mA
0.50 mA
0.75 mA
1.00 mA

A2 METERING DATA
MEASURED
AMMETER READING
(mA)
1
2
3
4
0 mA
250 mA
500 mA
750 mA
1000 mA
ANALOG INPUT1
ANALOG INPUT1:

ANALOG INPUT1
ANALOG INPUT1 MINIMUM:

ANALOG INPUT1
ANALOG INPUT1 MAXIMUM:
FORCE ANALOG OUTPUTS FUNCTION:

ANALOG OUTPUT 1 FORCED VALUE:
readings.

A2 METERING DATA
MEASURED
AMMETER
READING (mA)
1
2
3
4
:
ANALOG INPUTS
EXPECTED
MEASURED ANALOG
ANALOG
INPUT READING
INPUT
READING
1
2
"0-1 mA"
"0"
"1000" (repeat for
:
ANALOG INPUTS
EXPECTED
MEASURED ANALOG
ANALOG
INPUT READING
INPUT
READING
1
2
0 mA
250 mA
500 mA
750 mA
1000 mA
(units)
3
4
"0%"
(units)
3
4
7–9