GE 469 Instruction Manual page 295

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

CHAPTER 6: ACTUAL VALUES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
forgotten, contact the factory with the encrypted access code. See Passcode on page
5–8 for passcode features.
ACCESS DENIED, SHORT ACCESS SWITCH: In order to store any settings values, the
access switch must be shorted. If this message appears and it is necessary to change
a settings, short access terminals C1 and C2.
ALL POSSIBLE RESETS HAVE BEEN PERFORMED: If only some of the trip and alarm
features that are active can be cleared (i.e. the conditions that caused some of these
trips and/or alarms are still present), then this message will appear when a RESET is
performed, indicating that only trips and alarms that could be reset have been reset.
ARE YOU SURE? PRESS [ENTER] TO VERIFY: If the
of any trip or alarm feature is possible, this message will appear to ask for verification
of the operation. If
RESET
reset will be performed.
DATA CLEARED SUCCESSFULLY: This message confirms that data has been cleared or
reset in the
S1 469 SETUP
groups.
DATE ENTRY WAS NOT COMPLETE: Since the
DD/YYYY), if
is pressed before the complete value is entered, this message
ENTER
appears and the new value is not stored. Another attempt will have to be made with
the complete information.
DATE ENTRY WAS OUT OF RANGE: This message appears if and invalid entry is made
for the
(e.g. 15 entered for month).
DATE
DEFAULT MESSAGE HAS BEEN ADDED: Any time a new default message is added to
the default message list, this message will appear as verification.
DEFAULT MESSAGE HAS BEEN REMOVED: Any time a default message is removed
from the default message list, this message will appear as verification.
DEFAULT MESSAGE LIST IS FULL: If an attempt is made to add a new default message
to the default message list when 20 messages are already assigned, this message will
appear. In order to add a message, one of the existing messages must be removed.
DEFAULT MESSAGES 6 of 20 ARE ASSIGNED: This message appears each time the

469 SETUP
DEFAULT MESSAGES
number of assigned default messages.
END OF LIST: This message will indicate when the bottom of a subgroup has been
reached.
END OF PAGE: This message will indicate when the bottom of a page has been
reached.
ENTER NEW PASSCODE FOR ACCESS: If the passcode is zero, the passcode security
feature is disabled. If the Change Passcode settings is entered as yes, this flash
message will appear prompting the user to enter a non-zero passcode which in turn
will enable the feature.
INPUT FUNCTION IS ALREADY ASSIGNED: The Assignable Digital Input functions may
only be used once. If an attempt is made to assign the same function to two different
switches, this message will appear.
RESET
is pressed again while the message is still on the display, the
or

CLEAR DATA
S1 469 SETUP
DATE
settings group is entered. It notifies the user of the
key is pressed and resetting
settings

INSTALLATION
settings has a special format (MM/
S1
6–39

Advertisement

Table of Contents
loading

Table of Contents