Preset Motor Value - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

5.3.6
Preset Motor Values
 PRESET
MOTOR VALUES
5–24
STARTER STATUS
(Setpoint = 'Starter Auxiliary A')
REDUCED VOLTAGE STARTER AUXILIARY 'A' STATUS INPUT
STARTER STATUS
(Setpoint = 'Starter Auxiliary B')
REDUCED VOLTAGE STARTER AUXILIARY 'B' STATUS INPUT
FIGURE 5–3: Reduced Voltage Starter Inputs

PATH: SETTINGS
S2 SYSTEM SETUP
[]
MOTOR RUNNING HOURS
PRESET: 0
POS WATTHOURS PRESET:
MESSAGE
POS varHOURS PRESET:
MESSAGE
NEG varHOURS PRESET:
MESSAGE
The 469 can preset the following actual value accumulators. When an accumulator is
preset, 469 discards the previous value and continues to accumulate starting from the
new value.
Motor running hours
Display and set actual value shown in
ACTUAL VALUES > A4 MAINTENANCE > TIMERS > MOTOR RUNNING HOURS
Positive watt hours
Display and set actual value shown in
ACTUAL VALUES > A2 METERING DATA > POWER METERING > POSITIVE WATTHOURS
REDUCED VOLTAGE
AUXILIARY 'a'
D16
SWITCH INPUT
D23
D16
REDUCED VOLTAGE
AUXILIARY 'b'
SWITCH INPUT
FULL VOLTAGE
AUXILIARY 'b'
D23

PRESET MOTOR VALUES
0.000 MWh
0.000 Mvarh
0.000 Mvarh
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
FULL VOLTAGE
AUXILIARY 'a'
808723A1.CDR
Range: 0 to 99999 in steps of 1
Range: 0 to 999999.999 in steps of
.001
Range: 0 to 999999.999 in steps of
.001
Range: 0 to 999999.999 in steps of
.001