GE 469 Instruction Manual page 194

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

5–50
FIGURE 5–8: Thermal Limits for High Inertial Load
To illustrate the Voltage Dependent Overload Curve feature, the thermal limits of FIGURE
5–8: Thermal Limits for High Inertial Load will be used.
1.
Construct a custom curve for the running overload thermal limit. If the curve
does not extend to the acceleration thermal limits, extend it such that the curve
intersects the acceleration thermal limit curves (see the Custom Curve below).
2.
Enter the per unit current value for the acceleration overload curve intersect
with the custom curve for 80% line voltage. Also enter the per unit current and
safe stall protection time for 80% line voltage (see the Acceleration Curves
below).
3.
Enter the per unit current value for the acceleration overload curve intersect
with the custom curve for 100% line voltage. Also enter the per unit current and
safe stall protection time for 100% line voltage (see the Acceleration Curves
below).
CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL