CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
SPEED SWITCH TRIP
MESSAGE
SPEED2 DELAY: 5.0 s
SPEED2 RATED SPEED:
MESSAGE
3600 RPM
Two additional acceleration timers are provided for the two speed motor feature. One
timer is for a start in Speed 2 from a stopped condition. The other is an acceleration timer
for the transition from Speed 1 to Speed 2. Also, while the motor is running, the 469 will
ignore Mechanical Jam protection during the acceleration from Speed 1 to Speed 2 until
the motor current has dropped below Speed 2 FLA × Overload Pickup value, or the Speed
1-2 acceleration time has expired. At that point in time, the Mechanical Jam feature will be
enabled with the Speed 2 FLA.
Range: 1.0 to 250.0 s in steps of 0.1.
Seen only if one of the digital
inputs is assigned as Speed
Switch
Range: 100 to 7200 RPM in steps of 1.
Seen only if one of the digital
inputs is assigned as
Tachometer.