A3 Learned Data - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

CHAPTER 6: ACTUAL VALUES
6.4

A3 Learned Data

6.4.1
Motor Starting
 MOTOR
STARTING
6.4.2
Average Motor Load
 AVERAGE
MOTOR LOAD
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL

PATH: ACTUAL VALUES
[]
LEARNED ACCELERATION
TIME: 0.0 s
LEARNED STARTING
MESSAGE
CURRENT: 0 A
LEARNED STARTING
MESSAGE
CAPACITY: 0% used
LAST ACCELERATION
MESSAGE
TIME: 0.0 s
LAST STARTING
MESSAGE
CURRENT: 0 A
LAST STARTING
MESSAGE
CAPACITY: 0% used
The 469 learns the acceleration time, the starting current, as well as, the thermal capacity
required during motor starts. This data is accumulated based on the last five starts. The
469 also keeps statistics for last acceleration time, last starting current, and last starting
capacity. This information can be reset to default using the

RESET MOTOR INFORMATION
If motor load during starting is relatively consistent, the
may be used to fine tune the acceleration protection. Learned acceleration time will be the
longest time of the last five successful starts. The time is measured from the transition of
motor current from zero to greater than overload pickup, until line current falls below the
overload pickup level.
LEARNED STARTING CURRENT
from zero to greater than overload pickup. This should ensure that the measured current is
symmetrical. The value displayed is the average of the last 5 successful starts. If there are
less than 5 starts, 0s will be averaged in for the full 5 starts.
The
LEARNED STARTING CAPACITY
to permit a start (refer to Start Inhibit on page 5–68 for more information on start inhibit). If
there is not enough thermal capacity for a start, a start inhibit will be issued. Starting will
be blocked until there is sufficient thermal capacity.

PATH: ACTUAL VALUES
[]
AVERAGE MOTOR LOAD
LEARNED: 0.00 x FLA
A3 LEARNED DATA
MOTOR STARTING
settings.
is measured 200 ms after the transition of motor current
is used to determine if there is enough thermal capacity

A3 LEARNED DATA
AVERAGE MOTOR LOAD
Range: 0.0 to 200.0 sec.
Range: 0 to 50000 A
Range: 0 to 100%
Range: 0.0 to 200.0 sec.
Range: 0 to 50000 A
Range: 0 to 100%

S1 469 SETUP
INSTALLATION
LEARNED ACCELERATION TIME
Range: 0.00 to 20.00
6–27