SPEED2
OVERLOAD SETUP
5–108
SPEED2 TRIP AT
MESSAGE
7.50 x FLA: 6.3 s
SPEED2 TRIP AT
MESSAGE
8.00 x FLA: 5.6 s
SPEED2 TRIP AT
MESSAGE
10.0 x FLA: 5.6 s
SPEED2 TRIP AT
MESSAGE
15.0 x FLA: 5.6 s
SPEED2 TRIP AT
MESSAGE
20.0 x FLA: 5.6 s
Refer to Custom Overload Curve on page 5–44 for additional details on the custom
overload curves available for Speed2.
•
Voltage Dependent Overload Curves
If the
SELECT CURVE STYLE
following settings will appear:
PATH: SETTINGS
S14 2-SPEED MOTOR
[]
SPEED2 TRIP AT
1.01 x FLA: 17414.5 s
SPEED2 TRIP AT
MESSAGE
1.05 x FLA: 3414.9 s
SPEED2 TRIP AT
MESSAGE
1.10 x FLA: 1666.7 s
SPEED2 TRIP AT
MESSAGE
1.20 x FLA: 795.4 s
SPEED2 TRIP AT
MESSAGE
1.30 x FLA: 507.2 s
SPEED2 TRIP AT
MESSAGE
1.40 x FLA: 364.6 s
SPEED2 TRIP AT
MESSAGE
1.50 x FLA: 280.0 s
SPEED2 TRIP AT
MESSAGE
1.75 x FLA: 169.7 s
SPEED2 TRIP AT
MESSAGE
2.00 x FLA: 116.6 s
SPEED2 TRIP AT
MESSAGE
2.25 x FLA: 86.1 s
SPEED2 TRIP AT
MESSAGE
2.50 x FLA: 66.6 s
SPEED2 TRIP AT
MESSAGE
2.75 x FLA: 53.3 s
is set to "Voltage Dependent" in the Thermal Model, the
SPEED2 OVERLOAD SETUP
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1