7.2.7
Analog Inputs and Outputs
7–8
INPUT
ACCESS
TEST
STARTER STATUS
EMERGENCY RESTART
REMOTE RESET
ASSIGNABLE INPUT 1
ASSIGNABLE INPUT 2
ASSIGNABLE INPUT 3
ASSIGNABLE INPUT 4
TRIP COIL SUPERVISION
The 469 specification for analog input and analog output accuracy is ±1% of full scale.
Perform the steps below to verify accuracy. Verify the Analog Input +24 V DC with a
voltmeter.
4 to 20 mA Analog Input
 Alter the following settings:

S12 ANALOG I/O

S12 ANALOG I/O

S12 ANALOG I/O
value for Analog Inputs 2 to 4)
Analog output values should be ±0.2 mA on the ammeter. Measured analog input
values should be ±10 units.
 Force the analog outputs using the following settings:

S13 TESTING
TEST ANALOG OUTPUT
"Enabled"

S13 TESTING
TEST ANALOG OUTPUT
(enter desired value in percent; repeat for Analog Outputs 2 through 4)
 Verify the ammeter readings as well as the measured analog input
readings.
For the purposes of testing, the analog input is fed in from the analog
output (see FIGURE 7–1: Secondary Injection Test Setup on page 7–2).
 View the measured values in:

A1 STATUS
DIGITAL INPUTS
EXPECTED
PASS /
STATUS (SWITCH
FAIL
OPEN)
Open
Open
Open
Open
Open
Open
Open
Open
Open
No Coil
ANALOG INPUT1
ANALOG INPUT1:

ANALOG INPUT1
ANALOG INPUT1 MINIMUM:

ANALOG INPUT1
ANALOG INPUT1 MAXIMUM:
FORCE ANALOG OUTPUTS FUNCTION:

ANALOG OUTPUT 1 FORCED VALUE:
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 7: TESTING
EXPECTED
PASS /
STATUS (SWITCH
FAIL
CLOSED)
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Coil
"4-20 mA"
"0"
"1000" (repeat this
"0%"