Commissioning; Settings Table; Installation Information; Relay Settings - GE 735 Instruction Manual

Feeder protection relay
Table of Contents

Advertisement

7 COMMISSIONING

7 COMMISSIONING 7.1 SETTINGS TABLE
STATION NAME
EQUIPMENT DESIGNATION
VOLTAGE
DEVICE NUMBER
CT RATIO
ISSUE DATE
APPLIED DATE
735/737 SERIAL NUMBER
PHASE DIAL SETTINGS
Phase Pickup Dial (LO: 20 to 100% of CT; HI: 110 to 220% of CT; OFF)
Curve Shape Dial (MI, NI, VI, EI, Definite Time – HI/LO)
Phase Time Multiplier Dial (1 to 10)
Phase Instantaneous Dial (OFF, 4, 5, 6, 8, 10, 12, 14, 16, 20 x CT)
GROUND DIAL SETTINGS
Ground Pickup Dial (LO: 15 to 55% of CT; HI: 60 to 100% of CT; OFF)
Ground Shape Dial (MI, NI, VI, EI, Definite Time – HI/LO)
Ground Time Multiplier Dial (1 to 10)
Ground Instantaneous Dial (OFF, 0.1, 0.2, 0.4, 0.8, 1, 2, 4, 8, 16 x CT)
OPTION SWITCH SETTINGS
Phase O/C Shift Multiplier (0.5, 0.8, 1.0, 1.1)
Ground Time O/C Shift Multiplier (0.5, 0.8, 1.0, 1.1)
Frequency (50 Hz, 60 Hz)
Output Relays (Pulsed, Latched, Pickup, Pickup and Latched) – 737 only
Custom Scheme (Disabled, Enabled)
Custom Scheme > Time Overcurrent Curve Shape (ANSI, IAC, BS142)
Custom Scheme > Block Instantaneous on Autoreclose (Disabled, Enabled)
Custom Scheme > Aux Trip Relay (Main Trip, 86 Lockout, Ground Trip)
COMMUNICATIONS SETTINGS
Baud Rate
Communications Address
GE Power Management
735/737 Feeder Protection Relay

7.1 SETTINGS TABLE

7.1.1 INSTALLATION INFORMATION

7.1.2 RELAY SETTINGS

7
7-1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

737

Table of Contents