1.3.4

Enumeration Settings

1. SETPOINTS
Press [] for more
Press
or
MESSAGE
ENTER
SETPOINTS
[]
S1 469 SETUP
Press
MESSAGE
SETPOINTS
[]
S2 SYSTEM SETUP
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
 Therefore, press the
This flash message will momentarily appear as confirmation of the
storing process.
The example shown in the following figures illustrates the keypress sequences required to
enter system parameters such as the phase CT primary rating, ground CT primary rating,
bus VT connection type, secondary voltage, and VT ratio.
The following values will be entered:
Phase CT primary rating: 600 A
Motor Full Load Current: 318 A
Ground CT ratings: 50/5 A
Phase Differential CT: None
Voltage Transformer Connection Type: Open Delta
Motor Nameplate Voltage: 13800 V
VT Ratio: 115:1
To set the phase CT primary rating, modify the
settings as shown below.
PHASE CT PRIMARY
 Press the
header.
Press
CURRENT
MESSAGE
SENSING
or
ENTER
Press the
VALUE
or enter the value directly via the numeric
Press the
To set the phase Motor Full Load Amps FLA, modify the
SENSING  MOTOR FULL LOAD AMPS FLA
 Press the
header.
key to store the new value in memory.
ENTER
NEW SETPOINT HAS
BEEN STORED
S2 SYSTEM SETUP  CURRENT SENSING 
key until the relay displays the Sepoints menu
MENU
Press
[]
MESSAGE
or
ENTER
keys until 600 A is displayed,
keypad.
key to store the settings.
ENTER
S2 SYSTEM SETUP  CURRENT
settings as shown below.
key until the relay displays the Setpoints menu
MENU
PHASE CT PRIMARY:
OFF
PHASE CT PRIMARY:
600 A
NEW SETPOINT HAS
BEEN STORED