5.11.5 Reverse Power

 REVERSE
POWER
Note
5.11.6 Torque Setup
 TORQUE
SETUP
5–86

PATH: SETTINGS
S10 POWER ELEMENTS
[]
BLOCK REVERSE POWER
FROM START: 0 s
REVERSE POWER
MESSAGE
ALARM: Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
REVERSE POWER ALARM
MESSAGE
LEVEL: 2 kW
REVERSE POWER ALARM
MESSAGE
DELAY: 1 s
REVERSE POWER ALARM
MESSAGE
EVENTS: Off
REVERSE POWER
MESSAGE
TRIP: Off
ASSIGN TRIP RELAYS:
MESSAGE
Trip
REVERSE POWER TRIP
MESSAGE
LEVEL: 1 kW
REVERSE POWER TRIP
MESSAGE
DELAY: 1 s
If enabled, once the magnitude of 3-phase total power exceeds the Pickup Level in the
reverse direction (negative kW) for a period of time specified by the Delay, a trip or alarm
will occur.
The minimum magnitude of power measurement is determined by the phase CT minimum
of 5% rated CT primary. If the level for reverse power is set below that level, a trip or alarm
will only occur once the phase current exceeds the 5% cutoff.

PATH: SETTINGS
S10 POWER ELEMENTS
[]
TORQUE METERING
Disabled
STATOR RESISTANCE:
MESSAGE
0.004 mΩ
POLE PAIRS:
MESSAGE
2
TORQUE UNIT:
MESSAGE
Newton-meter
CHAPTER 5: SETTINGS

REVERSE POWER
Range: 0 to 50000 s in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
Range: 1 to 25000 kW in steps of 1
Range: 0.2 to 30.0 s in steps of 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 1 to 25000 kW in steps of 1
Range: 0.2 to 30.0 s in steps of 1

TORQUE SETUP
Range: Disabled, Enabled
Range: 0.001 to 50.000 mΩ in steps of
0.001
Range: 2 to 128 in steps of 1
Range: Newton-meter, Foot-pound
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL