To store the data press <ENT>. This moves the cursor to [20 mA].
To enable numeric entry press the <Right Arrow>. Type the numeric value corresponding to a 20
mA input signal. To store the data, press <ENT>.

5.10 THE METER FACILITIES MENU

Meter Facilities functions are available by using the magnetic wand to select <Meter Facilities>. The
Meter Facilities menu provides global control that enables you to identify and activate the following
functions and features of the hardware supported by this model. See Section 4 for menu structure.
Select data entry and meter output in either English (default) or metric units.
Customize the default pipe and transducer tables to suit your requirements.
Output, display, erase and select a memory management method for the Datalogger.
Determine the amount of memory available.
Verify/Adjust the analog output voltage and current using a multimeter.
Verify/Adjust the analog pulse output using a frequency counter.
Calibrate the RTD temperature sensors.
Set the system clock/calendar.
Obtain detailed software/hardware identification.
This menu allows you
to specify default
measurement units.
This menu allows you
to create or edit pipe
and transducer tables.
This menu allows you
to work with and
select a Datalogger
storage method.
This menu shows allows
you to calibrate the RTD
Temperature Sensors.
This menu shows detailed
information about this model's
hardware and software.

5.10.1 PREFERRED UNITS

The selection you make in this menu cell becomes the default units for all menu items and data outputs.
You can choose either English or metric units. The factory setting is English.
To specify metric default units for all meter functions:
To access the [Preferred Units] option list press
Move the cursor to [Metric] by pressing
To register your selection press
Siemens
Dual Path
Select Default Units for all Menus
Preferred Units
Table Setups
Datalogger Control
Memory Control
Analog Output Trim
RTD Calibrate
Clock Set
RS-232 Setup
Backlight
System Info
Meter Facilities
ENT
5-65
SITE 1
English
09.02.99 09.30.06
9600 Odd 7
On
CQO:1010PVXFM-3
This menu allows
you to view the
number of data
memory bytes.
This menu allows
you to fine-tune the
analog outputs.
This menu allows you
to set the system
clock/calendar.
This menu allows you
to select RS-232 port
parameters.