Section 5
PIPE TABLE MENU STRUCTURE (continued)

Create/Edit Pipe

Outer Diameter (in)
Wall Thickness
Liner Material
Liner Thickness
Delete Pipe
Choose Pipe Class
Choose Pipe Name
Create/Edit Pipe
The Pipe Table menu provides the primary data that the system uses to operate with different classes of
pipes. This menu allows you to edit the Pipe Table by modifying any existing pipe or add an entirely new
pipe.
The following is an example of how to use the [Create/Edit Pipe] menu cell function:
To access the [Create/Edit Pipe] menu press the <Right Arrow>.
To access the [Pipe Class] option list press the <Right Arrow>.
Press the <Up/Down Arrow> to scroll the option list to a class that provides the closest match to
your pipe.
To select the [Pipe Class] press <ENT>. This moves the highlight to the [Choose Pipe Name]
menu cell.
To access the [Pipe Name] option list press the <Right Arrow>.
Scroll the option list to a pipe name and press <ENT>to select it.
This loads [Outer Diameter (in)] and [Wall Thickness] menu cells for the selected pipe.
The highlight moves to [Outer Diameter (in)]. Press the <Right Arrow> to enable numeric entry.
Enter the actual pipe OD using the appropriate English or metric units.
Press <ENT> to store the OD. The highlight moves to [Wall Thickness].
Press the <Right Arrow> to enable numeric entry. Enter the actual wall thickness using the ap-
propriate English or metric units.
Press <ENT>to store the wall thickness.
Select a liner material from the [Liner Material] option list and enter its thickness (if required).
Press the <Left Arrow> to leave the Create/Edit Pipe menu. This triggers the [Save Pipe] prompt.
Note that the second line lists the name of the selected pipe.
Press the <Right Arrow> and then press <ENT> to use this name.
To use a new name, press the <Right Arrow> and then use the appropriate arrow keys or Mag-
netic Wand to rename the pipe (8 chars. Max.).
Press <ENT>. This adds the new pipe to the pipe class.
x.xxx (numeric entry)
x.xxx (numeric entry)
None
Cement
Coal Tar
Enamel
Glass
Plastic
HDPE
Teflon
Rubber
x.xxx (numeric entry)
*See Create/Edit Pipe
*See Create/Edit Pipe
5-68