■3. Address
GT Designer3 converts the device numbers into decimal format according to the address map of the MODBUS/RTU
slave equipment to be used.
The table below shows the representations on the MODBUS/RTU communication protocol and GT Designer3.
MODBUS/RTU Communication protocol
Device name
Coil
Input relay
Input register
Holding register
Extension file register
Function code to be used
Read
Write
0x05
0x01
0x0F
0x02
-
0x04
-
0x06
0x03
0x10
0x14
0x15
POINT
POINT
POINT
Address conversion example
When monitoring the holding register's address "1234H", GT Designer3 displays "4*****" since
GT Designer3 processes the internal conversion in decimal format as follows:
GT Designer3 converts the holding register's address "1234H" to "04660" in decimal format.
Then, "+1" is added to this decimal address since the holding register's address on GT
Designer3 always starts from "1."
Therefore, the holding register's address "1234H" is displayed as "404661" on GT Designer3.
Holding register
Address
0000
0001
to
FFFE
FFFF
0000
0001
to
FFFE
FFFF
0000
0001
to
FFFE
FFFF
0000
0001
to
FFFE
FFFF
0000
0001
to
270E
270F
1234H
"4 04660" +1
"404661"
5.6 Device Range that Can Be Set
Representation on GT Designer3
000001
000002
to
065535
065536
100001
100002
to
165535
165536
300001
300002
to
365535
365536
400001
400002
to
465535
465536
600000
600001
to
609998
609999
5 - 17