Sm Devices - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

2.4.6

SM devices

The SM devices are bit devices into which interrupt outputs and clock data that turn ON/OFF at 1-second cycles.
■1. List of SM devices
The following shows the SM devices (virtual devices inside the GOT).
Address
Interrupt output
When the ON/OFF state of SM0 to 49 is changed by a touch switch on the GOT, for example, the interrupt codes
shown below are transmitted (interrupt output) to the host side.
The data amount (number of bytes) to be interrupt-output is set at "Interrupt Data Byte" in "Communication Detail
Settings".
2.6.1 Setting communication interface (Controller Setting)
Address
SM0 to 49
1-second cycle clock
Turns ON/OFF at a 1-second cycle.
SM50
2-second cycle clock
Turns ON/OFF at a 2-second cycle.
SM51
Interrupt code output disable flag
Enables or disables the output of the interrupt code.
SM52
OFF: Interrupt code output enabledON: Interrupt code output disabled
When set to disable the interrupt code output, no interrupt data are output to the host.
(Relevant devices: D13, D14, SM0 to 49)
SM53 to 63
*1
*2
2 - 28
2.4 Device Data Area
Event type
Changed from OFF to ON
SM0
Changed from ON to OFF
Changed from OFF to ON
SM1
Changed from ON to OFF
Changed from OFF to ON
SM2
Changed from ON to OFF
Changed from OFF to ON
SM48
Changed from ON to OFF
Changed from OFF to ON
SM49
Changed from ON to OFF
0.5
0.5
1
1
After the ON/OFF state is changed, the interrupt data is output within a period of 1 to 10 ms.
When the ON/OFF state of SM0 to 49 is changed from the host side, interrupt output is not performed.
POINT
POINT
POINT
(1) The side where virtual devices are set
System:Set on the system side.
User:Set on the user side (by sending request messages from host or using the touch
switches, etc. on the GOT).
(2) Interrupt outputs (SM0 to 49)
• To disable the interrupt output, turn ON SM52 (interrupt code output disable flag).
2.4.6 SM devices
• To enable the interrupt output, set 8 bits to the data length at "Communication Detail
Settings".
2.6.1 Setting communication interface (Controller Setting)
• When "7 bits" is set, the MSB (8th bit) is ignored. (Example: FFH
Description
*1*2
Interrupt code
50
H
51
H
52
H
53
H
54
H
55
H
B0
H
B1
H
B2
H
B3
H
Unused
Set side