10.3.2
Communication detail settings
Make the settings according to the usage environment.
Item
GOT Net No.
*1
GOT Station
GOT
Communication Port No.
Retry
Startup Time
Timeout Time
Delay Time
Message Format
Communication data code
*2
Device read points
*2
Device write points
*2
Device read random points
*2
Device write random points
*1
Each of [GOT Station] set in the communication detail setting and [Station] set in the Ethernet setting must be set to different
station numbers.
10.3.4 Ethernet setting
*2
Pay attention to the following items for read/write points.
• Set the points to be processed at one-time communication.
• The point is in word device units. The point is to be 16 times of the set value for the bit device.
• The points could be less than the set value when UDP protocol or ASCII code are used.
• Refer to the following Technical News for details.
List of SLMP-compatible Equipment Validated to Operate with the GOT2000 Series (GOT-A-0085)
Description
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 1)
Set the GOT port No. for the connection with the Ethernet module.
(Default: 5031)
Set the number of retries to be performed when a communication timeout
occurs.
When receiving no response after retries, the communication times out.
(Default: 3times)
Specify the time period from the GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a communication to time out.
(Default: 3sec)
Set the delay time for reducing the load of the network/destination PLC.
(Default: 0ms)
Set the message format.
(Default: 4E frame)
Set the communication data code.
(Default: Binary code)
Set the device read points.
(Default: 960 points)
Set the device write points.
(Default: 960 points)
Device read random points
(Default: 0 point)
Device write random points
(Default: 0 point)
Range
1 to 239
1 to 120
1024 to 5010,
5014 to 49152,
49171 to 65534
(Except for 49153 to 49170)
0 to 5times
3 to 255sec
1 to 90sec
0 to 10000
(×10ms)
QnA compatible 3E frame, 4E frame
ASCII code, Binary code
1 to 960 points
1 to 960 points
0 to 192 points
0 to 160 points