Check Motor Rotation; Local-Control Test; System Start Up - Danfoss VLT AQUA Drive FC 200 Operating Instructions Manual

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Start Up and Functional Tes...
9.
Press [OK].
10.
Follow on-screen instructions.
11.
The test will run automatically and indicate when
it is complete.

3.5 Check Motor Rotation

Prior to running the frequency converter, check the motor
rotation. The motor will run briefly at 5Hz or the minimum
frequency set in 4-12 Motor Speed Low Limit [Hz].
1.
Press [Quick Menu].
2.
Scroll to Q2 Quick Setup.
3.
Press [OK].
4.
Scroll to 1-28 Motor Rotation Check.
5.
Press [OK].
6.
Scroll to Enable.
The following text will appear: Note! Motor may run in
wrong direction.
7.
Press [OK].
8.
Follow the on-screen instructions.
To change the direction of rotation, remove power to the
frequency converter and wait for power to discharge.
Reverse the connection of any two of the three motor
cables on the motor or frequency converter side of the
connection.

3.6 Local-control Test

CAUTION
MOTOR START!
Ensure that the motor, system, and any attached
equipment is ready for start. It is the responsibility of the
user to ensure safe operation under any operational
condition. Failure to ensure that the motor, system, and
any attached equipment is ready for start could result in
personal injury or equipment damage.
NOTE
The hand on key on the LCP provides a local start
command to the frequency converter. The OFF key
provides the stop function.
When operating in local mode, the up and down arrows
on the LCP increase and decrease the speed output of the
frequency converter. The left and right arrow keys move
the display cursor in the numeric display.
1.
Press [Hand ON].
2.
Accelerate the frequency converter by pressing
[
] to full speed. Moving the cursor left of the
decimal point provides quicker input changes.
®
VLT
AQUA Drive
Operating Instructions
If acceleration problems were encountered
If deceleration problems were encountered
See 8.4 Warning and Alarm Definitions for resetting the
frequency converter after a trip.
NOTE
3.1 Pre-start through 3.6 Local-control Test in this chapter
concludes the procedures for applying power to the
frequency converter, basic programming, set-up, and
functional testing.

3.7 System Start Up

The procedure in this section requires user-wiring and
application programming to be completed. 6 Application
Set Up Examples is intended to help with this task. Other
aids to application set-up are listed in 1.2 Additional
Resources. The following procedure is recommended after
application set-up by the user is completed.
®
MG.20.M8.02 - VLT
is a registered Danfoss trademark
3.
Note any acceleration problems.
4.
Press [OFF].
5.
Note any deceleration problems.
If warnings or alarms occur, see 8 Warnings and
Alarms
Check that motor data is entered correctly
Increase the ramp-up time in 3-41 Ramp 1 Ramp
Up Time
Increase current limit in 4-18 Current Limit
Increase torque limit in 4-16 Torque Limit Motor
Mode
If warnings or alarms occur, see 8 Warnings and
Alarms
Check that motor data is entered correctly
Increase the ramp-down time in 3-42 Ramp 1
Ramp Down Time
Enable overvoltage control in 2-17 Over-voltage
Control
3
3
27