See
"Locate a Faulty Power Supply" on page
8.
Verify that the following LEDs are not lit:
Service Required LED on the power supply
■
Front and rear Service Required LEDs
■
Rear PS Failure LED on the bezel of the server
■
See
"Interpreting LEDs" on page
Verify the power supply.
9.
See
"Verify a Power Supply" on page
Related Information
"Remove a Power Supply" on page 84
■
"Verify a Power Supply" on page 87
■
Verify a Power Supply
1.
Verify that the amber Service Required LED on the replaced power supply is not
lit.
2.
Verify that the PS Fault LED on the front of the server is not lit.
3.
Use the Oracle ILOM show faulty command to verify that the fault has been
cleared.
See
"Identify Faulted Components" on page 24
command.
Consider these possibilities.
If the previous steps did not clear the fault, see
■
for information about the tools and methods you can use to diagnose component faults.
If the previous steps indicate that no faults have been detected, then the component has been
■
replaced successfully. No further action is required.
Related Information
"Locate a Faulty Power Supply" on page 83
■
"Front Panel Components (Service)" on page 13
■
83.
29.
87.
for more information on using the show faulty
"Detecting and Managing Faults" on page 23