6.6.2

Connecting to YOKOGAWA PLC (STARDOM)

■1. System Configuration
YOKOGAWA
PLC
Connection cable
Communication
controller
Type
*1
STARDOM
Ethernet
(NFCP100,
NFJT100)
*1
*2
*3
*4
*5
6 - 16
6.6 Example of Connection
Hub
Connection cable
Max.
*5
Cable model
distance
Twisted pair cable
• 10BASE-T
Shielded
twisted pair
cable (STP) or
unshielded
twisted pair
cable (UTP):
100m
Category 3, 4,
and 5
• 100BASE-TX
Shielded
twisted pair
cable (STP):
Category 5 and
5e
When connecting STARDOM to MODBUS
For details, refer to the following manual.
YOKOGAWA PLC user's Manual
When connect a GOT to a PLC, connect to the PCL Ethernet port via a hub.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standards.
When connecting GT2000 to an equipment that meets the 10BASE (-T/2/5) standard, use the switching hub and operate in an
environment where 10Mbps and 100Mbps can be mixed.
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
Use the straight cable.
Connection cable
Connection cable
External
device
*5
Cable model
*4
Twisted pair cable
• 10BASE-T
Shielded
twisted pair
cable (STP) or
unshielded
twisted pair
cable (UTP):
*2
Hub
Category 3, 4,
and 5
• 100BASE-TX
Shielded
twisted pair
cable (STP):
Category 5 and
5e
®
/TCP, Modbus Communication Portfolio License is required.
Communication driver
GOT
*3
GOT
Max.
Option device
*4
distance
100m
- (Built into GOT)
MODBUS/TCP
Number of
connectable
GOT
equipment
Model
126 GOTs
for 1 PLC