■4. Error code list
In the case of formats 12 and 13 (Digital Electronics Corporation's memory link method (extended mode)), the details
(error code) of the error are appended to the response message during faulty communication.
The following shows error code, error contents, cause, and measures.
Error code
Sum check error
06H
The sum check code created from received data differs from
the sum check code in the receive data.
Command error
10H
An unsupported command was used.
Message length error
12H
The upper limit of the data length that can be received by the
GOT has been exceeded.
Clock data setting error
16H
The setting value of the clock data has error.
Address error
FAH
The start address of the read/write device is out of range.
Exceeded number of points error
FBH
The read/write range exceeded the device range.
Message format error
FCH
The format of the received message has error.
Timeout error
FFH
There is no response from the GOT, or the station of the
specified address does not exist.
■5. Precautions
(1) Batch reading/writing crossing over different devices
When using the batch read (R) or batch write (W) command, do not batch read/write crossing over the different
devices.
This will cause an error response.
(2) Storage order for 32-bit data
To use the program of Digital Electronics Corporation's memory link method with [32bit Order] setting to GOT1000
series, set [HL Order] to [32bit Order] for [Communication Detail Settings] when 32-bit data is set for GOT-A900
series.
With setting [LH Order], the order of upper bits and lower bits are reversed when the GOT displays and writes 32-bit
data.
Description
Action
• Review the contents of the message to transmit.
• Review the contents of the message to transmit.
• Check the commands in the message.
2.5.2 List of commands
• Review the contents of the message to transmit.
• Check the data length of the message.(data length of the data section,
etc.)
• Review the contents of the message to transmit.
• Check whether the non-existent data is set (e.g. setting "07" at the day of
the week) as clock data.
• Review the contents of the message to transmit.
• Check the devices that can be used and the device ranges.
2.4 Device Data Area
• Check the settings of "Communication Detail Settings".
• Review the contents of the message to transmit.
• Check the communication cable and communication module attachment.
• Check the settings of "Communication Detail Settings".
• Review the contents of the message to transmit.