Station Number Setting - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

5.5.2

Station number setting

In the MODBUS network, a maximum of 31 MODBUS
Assign a non-overlapped station number ranging from 1 to 247 arbitrarily to each MODBUS
In the system configuration, the MODBUS
included.
The station number can be set without regard to the cable connection order. There is no problem even if station numbers
are not consecutive.
■1. Direct specification
When setting the device, specify the station number of the MODBUS
■2. Indirect specification
When setting the device, indirectly specify the station number of the MODBUS
changed using the 16-bit GOT internal data register (GD10 to GD16).
When specifying the station No. from 248 to 254 on GT Designer3, the value of GD10 to GD16 compatible to the
station No. specification will be the station No. of the MODBUS
Specification station NO.
248
249
250
251
252
253
254
■3. All station specification (broadcast)
Target station differs depending on write-in operation or read-out operation.
• For write-in operation, all station will be a target.
• For read-out operation, only the host station will be a target.
®
/RTU equipment can be connected to one GOT.
®
/RTU equipment with the station number set with the host address must be
Station
GOT
No.3
Examples of station number setting
Specification range
1 to 247
Compatible device
GD10
GD11
0 to 255:
GD12
0 : All station specification (broadcast)
GD13
255 : Host station access
For the setting other than the above, an error (dedicated device is out of range) will
GD14
occur.
GD15
GD16
5.5 MODBUS(R)/RTU Equipment Side Setting
Station
Station
No.15
No.1
®
/RTU equipment of which data is to be changed.
®
/RTU equipment of which data is to be
®
/RTU equipment.
Setting range
®
/RTU equipment.
5 - 19
5