9 Troubleshooting and Maintenance

Error Descriptions

Event name
Unit Memory Error
Meaning
An error occurred when writing to internal memory where the error history is saved.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
There is a source of noise nearby.
Non-volatile memory failure
Attached
None
information
Precautions/
You can change the event level to the observation level. If you change the level to the observation level, the Recovery
Remarks
column above will be changed to "Error reset."
Event name
Network Power Error
Meaning
Network power is not being supplied.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Communications power is not being
supplied normally from the network.
Attached
None
information
Precautions/
None
Remarks
9-42
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Implement noise countermeasures.
If the above cause does not apply,
replace the Unit.
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Check the network power supply and
network cable connections and cor-
rect any errors.
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
Event code
0488 0000 hex
CJ-series Unit
Detection
timing
Cycle the power
Log category
supply.
Non-volatile memory cannot be written.
Name
---
Prevention
Use the Controller away from sources
of noise.
None
Event code
0489 0000 hex
CJ-series Unit
Detection
timing
Cycle the power
Log category
supply.
The DeviceNet Unit will stop remote I/O communications
and return errors for message send requests whenever
there is a network power supply error. When the network
power supply returns to normal status, the error display
will stop, the scan will be started, and message process-
ing will return to normal. The scan will not start again after
recovery to normal operation, however, if remote I/O com-
munications are set to stop when a communications error
occurs.
Name
---
Prevention
Check to see if the network power
supply and network cables are cor-
rectly wired.
At power ON,
Controller reset,
or error history
save
System
Continuously
System