Omron CJ1W-DRM21 Operation Manual page 252

Machine automation controller cj-series, nj-series cpu unit
Hide thumbs Also See for CJ1W-DRM21:
Table of Contents

Advertisement

9 Troubleshooting and Maintenance
Indicators
MS
NS
7-seg-
ment
Red
-
HA
(flashing)
Red
-
Hb
(flashing)
Red
-
HC
(flashing)
Red
-
Hd
(flashing)
*1 The 7-segment indicator will alternate between the Unit's node address and the code given in the tables in this section.
9-22
Error
Error
category
*1
CPU Unit
CPU Unit
exchange
memory
faulty
CPU Unit
faulty (Hb)
Routing
table logic
error
I/O refresh
error
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
Likely cause
A parity error occurred
while reading the routing
table.
A timeout occurred while
reading the routing table.
There is an error in the
contents of the routing
table.
• The I/O areas set in the
master scan list or slave
scan list do not exist in
the CPU Unit.
• This error can occur
when the Unit is
mounted to a different
CPU Unit with a different
number of EM banks or
EM that has been con-
verted to file memory.
Note This error may occur
during
remote
I/O
communications, too.
DeviceNet Unit
response
• Records the error in the
error log and continues
processing
• The routing table is
treated as missing.
• Continues processing
but data exchange with
the CPU Unit is stopped.
• The routing table is
treated as missing.
• Records the error in the
error log.
• Records the error in the
error log.
• The routing table is
treated as missing and
processing continues.
Stops remote I/O commu-
nications for the function
(master or slave) using the
non-existent area.
Note There is a possibility
that this error will
occur again. If it
does occur again,
restart remote I/O
communications
to
return the system to
normal operation.
Error
log
(Hex)
0012
0011
021A
0347