Errors That May Occur In Remote I/O Communications - Omron CJ1W-DRM21 Operation Manual

Machine automation controller cj-series, nj-series cpu unit
Hide thumbs Also See for CJ1W-DRM21:
Table of Contents

Advertisement

4-7
Errors that May Occur in Remote I/O
Communications
The following errors may occur during remote I/O communications.
Condition
Error
Error
*_Mstr1StruE
occurs in
rr (Structure
fixed allo-
Error) is
cations
TRUE
with the
scan list
disabled
Error
*_Mstr1VefyE
occurs in
rr (Verifica-
either fixed
tion Error) is
or user-set
TRUE
alloca-
tions with
the scan
list
enabled
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
Details
Duplicate
The same I/O word is allocated to
I/O area
two or more slaves. (This occurs
whenever a slave that is allocated
multiple words has one of the
words allocated to the node
address of another Slave.)
I/O area
A slave is allocated an area out-
range
side the fixed allocations area.
exceeded
(This occurs whenever slaves are
allocated multiple words and a
slave is allocated a word beyond
node address 63 in the fixed allo-
cations area.)
Unsup-
The I/O size of a slave exceeds
ported
200 bytes (100 words). (This
Slave
occurs if either the IN or the OUT
size exceeds 200 bytes.)
No slaves
A Slave registered in the scan list
present
is not present.
I/O size
The I/O size registered in the scan
mis-
list does not match the I/O size of
matched
the slave.
Note I/O size is compared in 8-
point (1-byte) units. If I/O
size is registered at 8 points
for example, then an error
I/O size mismatch will not
occur with a Slave with just
one input point connected.
Incorrect
The vendor registered in the scan
vendor
list does not match the slave ven-
dor.
Incorrect
The device type registered in the
device type
scan list does not match the slave
device type.
Incorrect
The product code registered in
product
the scan list does not match the
code
slave product code.
Incorrect
The connection bus registered in
connection
the scan list is set incorrectly.
bus
Unsup-
The slave does not support the
ported con-
connection registered in the scan
nection
list.
4 Remote I/O Master Communications
Results
Reconnect with
the error slave
and continue
remote I/O com-
munications.
Indicators
7-seg-
ment
indica-
tor
MS: Not
d0
related
NS:
Flashes
red
d1
d2
d5
d6
d6
d6
d6
d6
d6
4-33