Appendices
Connections Using Allocations
Allocation method
With CX-
Integrator
Without CX-
Integrator
Setting Connection Type
The settings for remote I/O communications connections differ depending on the allocation method,
as outlined below.
Fixed Allocations or User-set Allocations Using Device Variable for CJ-series
Unit
The Master CJ-series DeviceNet Unit automatically selects either poll or bit-strobe, whichever
makes the communications cycle time shortest.
User-set Allocations Using the CX-Integrator
The Master CJ-series DeviceNet Unit can make an automatic selection, the same as above, or the
user can select up to two connections for a Slave. The setting method is outlined below.
1
Select the Master Node in the Network Configuration Window in the CX-Integrator.
2
Select Device – Parameters – Edit – All Masters and select the corresponding Slave. Click the
Detailed Settings Button.
3
On the Connection Tab Page shown below, select a check box.
• Automatic selection
• User selection
Select up to two connections from poll, bit–strobe, COS and cyclic. COS and cyclic connec-
tions cannot be used at the same time.
A-36
User-set allocations
The user can select the connection to be used for each node address
from the CX-Integra-
with the CX-Integrator e.g., poll could be used for data and COS
tor
could be used for status. You can specify automatic selection or user
selection. You can use two connections simultaneously for one slave
(but you cannot use COS and cyclic simultaneously.)
Fixed allocation
Only 1 connection, automatically selected by the DeviceNet Unit.
(scan list disabled or
(Either a polling or bit-strobe connection is used.)
enabled)
User-set allocations
Only 1 connection, automatically selected by the DeviceNet Unit
using device vari-
based on the I/O area set in the Master User-set Allocations Setup
ables for CJ-series
Table.
Unit