Omron CJ1W-DRM21 Operation Manual page 246

Machine automation controller cj-series, nj-series cpu unit
Hide thumbs Also See for CJ1W-DRM21:
Table of Contents

Advertisement

9 Troubleshooting and Maintenance
Indicators
MS
NS
7-seg-
ment
Red
-
E8
(flashing)
*1 The 7-segment indicator will alternate between the Unit's node address and the code given in the tables in this section.
9-16
Error
Error
category
*1
Memory
Master
access
scan list
logic error
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
Likely cause
There is an error in the
contents of the master
scan list stored in non-vol-
atile memory.
DeviceNet Unit
response
• Records the error in the
error log.
• The master remote I/O
communications will be
stopped.
• Data exchange, slave
operation, and message
communications with the
CPU Unit will continue.
Normal operation will
resume when the master
scan list is written nor-
mally. (Start the master
remote I/O communica-
tions.)
Error
log
(Hex)
021A