7 Troubleshooting

Error Descriptions

Event name
Registration Table Verification Error
Meaning
An inconsistency was found when verifying the slave registration table.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
There is at least one entry in the slave
registration table where the node
address and Slave Unit model are
inconsistent.
Attached
None
information
Precautions/
If pin 4 (REGS) on the DIP switch on the Master Unit is ON when the power is turned ON or the Controller is reset, the
Remarks
registration table is enabled.
Event name
Slave Unit Duplicated Address Error
Meaning
The same address is used by more than one Slave Unit or the same word has been allocated to more than one Slave
Unit.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The same node address is set for
more than one Slave Unit.
There are no duplicated node
addresses set for the Slave Units, but
allocated words overlap.
A Slave Unit was disconnected from
the network, and then another Slave
Unit with the same node address but
a different I/O capacity joined the net-
work.
Attached
None
information
Precautions/
None
Remarks
7-14
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Correct the registration table so that
all node addresses and Slave Unit
models are consistent. If verification
of the registration table is not
required, disable verification of the
registration table.
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Turn OFF the power supply to the
Master Unit and Slave Units, and then
change the settings so that there are
no duplicated node addresses or
overlapping word allocations.
CJ-series CompoNet Master Unit Operation Manual for NJ-series CPU Unit (Cat. No. W493)
Event code
349C 0000 hex
CJ-series Unit
Detection
timing
Error reset
Log category
Even if this error occurs, remote I/O communications start
for the Master Unit. Remote I/O communications are not
possible for the Slave Unit. If a Slave Unit is missing, mon-
itoring for Slave Unit participation will continue. When the
Slave Unit joins the network, normal status is recovered. If
there is an unregistered Slave Unit in the network, normal
status is recovered by correcting the registration table and
cycling the power supply.
Name
---
Prevention
Create the registration table so that all
node addresses and Slave Unit mod-
els are consistent.
Event code
349D 0000 hex
CJ-series Unit
Detection
timing
Error reset
Log category
Even if this error occurs, remote I/O communications start
for the Master Unit. However, communications are not
possible for the Slave Units with duplicated addresses.
Name
---
Prevention
Do not use the same address for
more than one Slave Unit and make
sure that allocated words do not over-
lap.
At power ON
System
During Compo-
Net communica-
tions
System

Advertisement