4 Remote I/O Master Communications
Allocation Procedures
Step 1: Set the CPU Unit to PROGRAM Mode.
Step 2: Set the Master Enable Switch to TRUE.
Make sure that master communications was disabled by checking to see if *_MstrEnblSta (Master
Function Enabled Status) is FALSE, and then set to TRUE the *_Sw1MstrEnblCmd (Master Enable
Switch) to enable master communications. Once you have turned this switch from OFF to ON, which
will enable the master, the system operates over the master whether the power supply is turned OFF
or ON.
Note Do not change the Master Enable Switch to TRUE unless master communications are
stopped. (If the Master Enable Switch is change to TRUE when master communications are
enabled, a Unit error will occur and a "C5" error will be displayed on the 7-segment indicator
on the front panel.)
Step 3: Set the Master User-set Allocations Setup Table
This table specifies the area and first word for each block and the area and first word for the Alloca-
tion Size Setup Table.
• Master User-set Allocations Setup Table
Name of device variables for
CJ-series Unit
*_MstrAlocTblCfg[0]
*_MstrAlocTblCfg[1]
*_MstrAlocTblCfg[2]
*_MstrAlocTblCfg[3]
*_MstrAlocTblCfg[4]
*_MstrAlocTblCfg[5]
*_MstrAlocTblCfgSta
• Areas and Word Ranges for OUT Block 1, IN Block 1, and the Allocation Size Setup Table
Code
0
1
3
4
5
8 to 20
Note You cannot use Holding Area H512 and its subsequent holding areas, or EM Area Bank D and its subse-
quent banks.
4-26
Type
UINT
OUT block 1 area
UINT
First word in OUT block 1
UINT
IN block 1 area
UINT
First word in IN block 1
UINT
Allocation size setup table area
UINT
First word in allocation size setup table 1
WORD
Setting Results of Master User-set Alloca-
tions Setup
Area name in memory used
for CJ-series Unit
---
CIO Area (CIO)
Data Memory (DM)
Work (WR)
HR (HR)
Expansion Data Memory (EM)
Bank 0 to bank C (13 banks)
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
Name
0 to 20
0 to 32767
0 to 20
0 to 32767
0 to 20
0 to 32767
16#0000 to FFFF
Word range
The block is not used.
0 to 6143
0 to 32767
0 to 511
0 to 511
0 to 32767 (E0_00000 to E0_32767,
... , EC_00000 to EC_32767) for all
banks
Range