Omron CJ1W-DRM21 Operation Manual page 275

Machine automation controller cj-series, nj-series cpu unit
Hide thumbs Also See for CJ1W-DRM21:
Table of Contents

Advertisement

Event name
Verification Error
Meaning
The slave information registered in the scan list does not agree with the actual slave information.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
A slave that is in the scan list does not
exist.
• The master and slaves have differ-
ent communications settings.
• Communications cable lengths
(trunk line and branch lines) are
unsuitable.
• A communications cable is discon-
nected or loose.
• The terminating resistance is some-
where other than the ends of the
trunk line.
• Noise
The node address of the local Unit,
which is the master, is registered in
the scan list.
If the system is set to check the ven-
dor in the detailed verification set-
tings, the vendor of the slave does not
match the registration in the scan list.
If the connection path is set in the
detailed verification settings, then set-
ting the connection path that is set in
the scan list failed.
The size of the slave I/O data does
not match the registration in the scan
list.
If the device type is set in the detailed
verification settings, then setting the
device type that is set in the scan list
failed.
If the product code is set in the
detailed verification settings, then set-
ting the product code that is set in the
scan list failed.
The device does not support the I/O
service specified in the scan list.
Attached
None
information
Precautions/
None
Remarks
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
• Correct the settings so that the
master and slaves use the same
baud rate.
• Adjust the communications cables
of the trunk and branch lines to suit-
able lengths.
• Connect the communications cable
securely. If the communications
cable is broken, replace it.
• Connect terminating resistance only
to the ends of the trunk line.
• Implement noise countermeasures.
Do not register the node address of
the local Unit in the scan list.
Correct the scan list if the slave is cor-
rect. If the slave is incorrect, replace it
with the correct slave.
9 Troubleshooting and Maintenance
Event code
34BD0000 hex
CJ-series Unit
Detection
timing
Error reset
Log category
The DeviceNet Unit periodically performs reconnection
processing for slaves.
Name
---
Prevention
• Set the master and slaves to the
same baud rate.
• Install suitable lengths of communi-
cations cables for the trunk and
branch lines.
• Connect the communications cable
securely. Check to see if the com-
munications cable is broken.
• Connect terminating resistance only
to the ends of the trunk line.
• Implement noise countermeasures.
Do not register the node address of
the local Unit in the scan list.
Make sure that the information in the
scan list matches the information of
the slaves that are actually con-
nected.
When trying to
establish an ID
connection
System
9
9-45