Omron CJ1W-DRM21 Operation Manual page 103

Machine automation controller cj-series, nj-series cpu unit
Hide thumbs Also See for CJ1W-DRM21:
Table of Contents

Advertisement

Name of device variable for
CJ-series Unit
*_SlavFunErr
*_MemErr
*_BusoffErr
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
3 Data Exchange with the CPU Unit
Type
R/W
Area
BOOL
R
Slave Func-
tion Error
BOOL
R
Unit Mem-
ory Error
BOOL
R
Bus Off
Error
Function
<Operation specifications>
TRUE:
Indicates that at least one slave error
occurred. Refer to *_Slav1Sta (Slave Sta-
tus 1).
The slave errors are as follows:
• *_Slav1IO1Err (Remote I/O Communi-
cations Error with slave communications
enabled, for OUT 1/IN 1)
• *_Slav1IO2Err (Remote I/O Communi-
cations Error with slave communications
enabled, for OUT 2/IN 2)
• *_Slav1FunDatErr (Invalid Setup Data)
• *_Slav1IORefErr (Slave I/O Refresh
Error)
FALSE:
Indicates that none of the above errors
occured. Or, changes to FALSE when all
of above errors are cleared.
Default: FALSE
<Operation specifications>
TRUE:
Indicates an error in internal memory
where the error history is stored. (The
error occurs when the Unit starts up or
when the error history is written.)
FALSE:
Indicates that the error did not occur.
Once this error occurs, the bit will remain
TRUE and will not return to FALSE (Nor-
mal).
Default: FALSE
<Operation specifications>
TRUE:
Indicates that a Bus OFF error (communi-
cations were stopped by multiple data
errors) occurred.
When a Bus OFF occurs, the Unit goes
offline and all communications stop
(remote I/O communications are stopped,
slave operation is stopped, and message
communications are disabled).
FALSE:
Indicates that the error did not occur.
Once this error occurred, the bit will
remain TRUE and will not return to FALSE
(Normal).
Default: FALSE
3
3-27