Omron CJ1W-DRM21 Operation Manual page 253

Machine automation controller cj-series, nj-series cpu unit
Hide thumbs Also See for CJ1W-DRM21:
Table of Contents

Advertisement

Status of C200H Master Replacement
Master Status 1
*_CMstrSta*_CMstrSta
*_CMstrErr (Master Error) and
*_CMstrCfgErr (Configuration Error) are
TRUE.
*_CMstrErr (Master Error) and
*_CMstrCfgErr (Configuration Error) are
TRUE.
*_CMstrErr (Master Error) and
*_CMstrCfgErr (Configuration Error) are
TRUE.
*_CMstrErr (Master Error) and
*_CMstrCfgErr (Configuration Error) are
TRUE.
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
Status of device variables
for CJ-series Units
*_RTblErr (Routing Table Error) and
*_UnitErr (Unit Error) are TRUE.
*_RTblErr (Routing Table Error) and
*_UnitErr (Unit Error) are TRUE.
*_RTblErr (Routing Table Error) and
*_UnitErr (Unit Error) are TRUE.
*_UnitErr (Unit Error), *_MstrFunErr
(Master Function Error) and
*_Mstr1IORefErr (Master I/O Refresh
Error) are TRUE, or *_UnitErr (Unit
Error), *_SlavFunErr (Slave Function
Flag) and *_Slav1IORefErr (Slave I/O
Refresh Error) are TRUE.
9 Troubleshooting and Maintenance
Correction
Register the routing table in the CPU
Unit again and restart the Controller.
Replace the CPU Unit if the error
recurs.
Register the routing table in the CPU
Unit again and restart the Controller.
Replace the CPU Unit if the error
recurs.
Set the routing table in the CPU Unit
correctly and restart the DeviceNet
Units.
Check the master scan list and slave
scan list and reset with a correct allo-
cation.
9
9-23