Omron CJ1W-DRM21 Operation Manual page 239

Machine automation controller cj-series, nj-series cpu unit
Hide thumbs Also See for CJ1W-DRM21:
Table of Contents

Advertisement

Status of C200H Master Replacement
Master Status 1
*_CMstrSta*_CMstrSta
*_CMstrErr (Master Error) and
*_CMstrStruErr (Structure Error) are
TRUE.
*_CMstrErr (Master Error) and
*_CMstrVefyErr (Verification Error) are
TRUE.
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
Status of device variables
for CJ-series Units
*_Mstr1StruErr (Structure Error),
*_UnitErr (Unit Error) and *_MstrFunErr
(Master Function Error) are TRUE.
*_Mstr1VefyErr (Verification Error),
*_UnitErr (Unit Error) and *_MstrFunErr
(Master Function Error) are TRUE.
9 Troubleshooting and Maintenance
Correction
Use slaves with input and output
areas of 200 bytes max.
Check the following:
• Matching master and slave baud
rates
• Proper cable lengths (trunk and
branch lines)
• Broken or loose cables
• Installation of terminators only at
both ends of the trunk line
• Excessive noise
9
9-9

Hide quick links: