Replacing Faulty Units - Omron CJ1W-DRM21 Operation Manual

Machine automation controller cj-series, nj-series cpu unit
Hide thumbs Also See for CJ1W-DRM21:
Table of Contents

Advertisement

Installation
9-5-3

Replacing Faulty Units

Replace a DeviceNet Unit with an error as soon as possible. Refer to the DRT2 Series DeviceNet
Slaves Operation Manual (Cat. No. W404) or the DeviceNet MULTIPLE I/O TERMINAL Operation Man-
ual (Cat. No. W348) for details on replacing slaves. We recommend having spare Units available to
restore network operation as quickly as possible.
Precautions
Observe the following precautions when replacing a faulty Unit.
• After replacement make sure that there are no errors with the new Unit.
• When a Unit is being returned for repair, attach a sheet of paper detailing the problem and return
the Unit to your OMRON dealer.
• If there is a faulty contact, try wiping the contact with a clean, lint-free cloth dampened with alco-
hol.
Precautions for Safe Use
To prevent electric shock when replacing a Unit, be sure to stop communications in the network
and turn OFF the power supplies to all of the nodes (master and slaves) before removing the
faulty Unit.
Settings after Replacing DeviceNet Units
When the master communication is used, the scan list (project file) must be registered again.
All of the settings data stored in the DeviceNet Unit can be saved to the CPU Unit's SD Memory
1
Card*
and later read from the SD Memory Card*
save all of the settings data when the Unit is operating normally.
*1 Change *_Sw2FileBkupCmd (Unit Setup File Backup Switch) to TRUE.
*2 Change *_Sw2FileRestoreCmd (Unit Setup File Restore Switch) to TRUE.
The backup file is saved to the CPU Unit's SD Memory Card with the filename DNnnBKUP.dvf. (The
number "nn" is the unit number in 2-digit hexadecimal.)
Fixed Remote I/O Allocations
Turn ON power to all slaves and then select one of the fixed allocations areas (1, 2, or 3) and change
*_Sw1SListEnblCmd (Scan List Enable Switch) of software switch 1 to TRUE. The scan list will be
registered.
For details on allocation procedures, refer to 4-3-2 Allocation Procedures.
User-set Remote I/O Allocations
Use one of the following procedures.
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
Item
Are the Units installed securely?
Are the communications connec-
tors fully inserted?
Are the external wiring screws
tight?
Are the connecting cables
undamaged?
9 Troubleshooting and Maintenance
Standard
Equipment
No looseness
Phillips head
screwdriver
No looseness
Phillips head
screwdriver
No looseness
Phillips head
screwdriver
No damage
Check visually
2
. It will be much easier to replace the Unit if you
9
9-61